WEB Configuration Utility
6.1 WEB Configuration Utility
F US Clamp-on Communications Protocol Manual
64
Hardware Installation Manual, 11/2015, A5E34981613-AC
__Dev_Name
This parameter can be used to change the default BACnet Device Name of the node. The
default names include the communication (IP or MSTP), the meter type, and the firmware
type. This name may have to be changed to make the name unique system wide.
Modbus Parameters
Figure 6-3
Modbus Settings
mod_parity
This parameter sets the communication parity on the Modbus RS485 network. Acceptable
entries include “None, Odd, Even”. None is the default. This parameter will display the
current setting for Modbus RS485 communication.
mod_data_bits
This parameter sets the number of communication data bits on the Modbus RS485 network.
Acceptable entries include “8, 7”. 8 is the default. This parameter will display the current
setting for the Modbus RS485 communication.
mod_stop_bits
This parameter sets the number of communication stop bits on the Modbus RS485 network.
Acceptable entries include “1, 2”. 1 is the default. This parameter will display the current
setting for the Modbus RS485 communication.