Connecting
5
This chapter describes how to wire up the device without bus communication.
In order to wire up devices with communication modules, e.g. HART, Profibus PA or DP,
Foundation Fieldbus, DeviceNet or MODBUS, refer to the Operating Instructions for relevant
add-on module.
1
2
3
4
5
6
7
①
Magnetic coil cable to sensor
②
Terminal box for power supply and output signal cables
③
Potential equalization
④
Output signal cable
⑤
Power supply
⑥
Electrode cable to sensor
⑦
Terminal box for magnetic coil and electrode cables
Figure 5-1
Overview, Electrical connections
Cable specifications
● Only use cables with at least the same degree of protection as the sensor to install the
sensor.
● The cable length from the cable gland to the terminals must be kept as short as possible.
Cable loops in the terminal box must be avoided.
● To guarantee the IP 67/NEMA 4 degree of protection, use cables with external diameters
matching the used cable glands.
SITRANS MAG 6000 I/6000 I Ex de
Operating Instructions, 08/2018,
A5E02083319-AH
29