WARNING
Wire insulation
The insulation between the connected mains supply and the low voltage supply for the
flowmeter must be rated with at least double or reinforced insulation at mains voltage.
For field wiring installation: Ensure that the National Installation Code of the country in which
the flowmeters are installed is met.
1. Replace blind plug with cable gland.
2. Push power supply cable through open gland.
3. Connect power supply to L1, N and protective earth (PE) and tighten cable strap (C).
C
4. Tighten cable gland for power supply cable (approx. 20 Nm).
Connecting output signal cable(s)
If no output signals are needed, proceed with "Finishing connection".
CAUTION
Pulse output
The pulse output must be connected to equipment complying with Low Voltage Directive in
order to be considered safe. The isolation within FUS080 pulse output is only a functional
isolation.
1. Replace blind plug with cable gland (if two output signals are required, use a double entry
cable gland).
2. Push output cable(s) through open gland.
Connecting
5.3 Remote system
FUS380/FUE380
Operating Instructions, 09/2016, A5E00730100-AB
41
Содержание SITRANS F FUE380
Страница 6: ...Table of contents FUS380 FUE380 6 Operating Instructions 09 2016 A5E00730100 AB ...
Страница 20: ...Description 3 5 Principle of operation FUS380 FUE380 20 Operating Instructions 09 2016 A5E00730100 AB ...
Страница 62: ...Functions 7 4 Hardware key FUS380 FUE380 62 Operating Instructions 09 2016 A5E00730100 AB ...
Страница 78: ...Troubleshooting FAQs 9 2 Diagnosing with PDM FUS380 FUE380 78 Operating Instructions 09 2016 A5E00730100 AB ...
Страница 100: ...Settings B 3 Ordering of spare parts FUS380 FUE380 100 Operating Instructions 09 2016 A5E00730100 AB ...