
Commissioning
6.6 Commissioning via local display
SITRANS F Ultrasonic flowmeters FST030 (HART)
Operating Instructions, 08/2017, A5E35971532-AC
59
Text
Options/Description
Medium settings
Select "Yes" to configure the medium.
Medium settings
Select the process medium.
Process parameters
Set the expected sound velocity (only available if custom process medi-
um is selected) and the process temperature, pressure, kinetic viscosity,
and density.
Note
Important!
The entry of fixed process kinematic viscosity and/or fixed process density in this menu will
be ignored for the following cases:
1.
One or more analog input are enabled and assigned to either "density" and/or "kinematic
viscosity". This overrides the corresponding fixed process values.
2.
The Hydrocarbon table calculation for density and/or viscosity are enabled (applies only
to the Hydrocarbon meter variant). This overrides the corresponding fixed process
values.