Description
3.5 HART communication
SITRANS F Ultrasonic flowmeters FST030 (HART)
26
Operating Instructions, 08/2017, A5E35971532-AC
Download EDD files (
http://www.siemens.com/flowdocumentation
Configuration of the HART polling address
The HART address can be set either via hardware (DIP switch) or via software (local display
or SIMATIC PDM).
The DIP switch is located on the transmitter cassette.
Figure 3-2
HART slave address switch
●
Configuration via DIP switch (HW polling address)
Set 1 to 15 on the DIP switch if you wish to set a fixed (hardware-defined) HART polling
address (SW polling address will be ignored). The configured HW polling address can be
read via HMI in menu item 4.2.
●
Configuration via the local display or SIMATIC PDM (SW polling address)
Disable the HW polling address by setting all switches to "OFF" on the HART DIP switch.
The device starts up with default slave address = 0. The SW polling address can be
changed to a value between 0 and 63 via HMI (menu item 4.1) or SIMATIC PDM
DIP switch configuration
Table 3- 2
HW polling address
Address
Switch 1
Switch 2
Switch 3
Switch 4
0
0
0
0
0
1
1
0
0
0
2
0
1
0
0
3
1
1
0
0
4
0
0
1
0
5
1
0
1
0
6
0
1
1
0
7
1
1
1
0
8
0
0
0
1
9
1
0
0
1
10
0
1
0
1
11
1
1
0
1
12
0
0
1
1
13
1
0
1
1
14
0
1
1
1
15
1
1
1
1
0: OFF; 1: ON