Diagnosing and troubleshooting
9.4 Fault codes and corrective actions
SITRANS F Ultrasonic flowmeters FST030 (HART)
98
Operating Instructions, 08/2017, A5E35971532-AC
ID/
Icons
Diagnostic
Action
Comment
159
Internal error
Internal error in transmitter. Turn off the power,
wait 5 seconds and turn on the power again. If
the error still exists, contact your local Sie-
mens representative.
160
Mass flow
Value simulated. Disable 'Simulation' before
returning to normal operation
161
Volume flow
Value simulated. Disable 'Simulation' before
returning to normal operation
162
Density
Value simulated. Disable 'Simulation' before
returning to normal operation
163
Medium temperature
Value simulated. Disable 'Simulation' before
returning to normal operation
166
Standard volume flow
Value simulated. Disable 'Simulation' before
returning to normal operation
Only hydrocarbon
167
Totalizer 1
Value simulated. Disable 'Simulation' before
returning to normal operation
168
Totalizer 2
Value simulated. Disable 'Simulation' before
returning to normal operation
169
Totalizer 3
Value simulated. Disable 'Simulation' before
returning to normal operation