Commissioning
10.2 AS-Interface
SIRIUS 3RA6 Compact Starter
System Manual, 02/2008, GWA 4NEB 560 0601-02 DS 02
83
Procedure
The AS-i mounting module is addressed via an addressing socket, e.g. using the
AS-Interface addressing unit. The connecting cable is used to connect this unit to the
addressing socket.
Step
Instructions
Image
1
If the AS-i mounting module on the
compact starter is to be addressed via
the addressing socket, remember to
switch off the AS-i voltage. This is
necessary for reasons of plant safety.
2
Connect the AS-Interface addressing
unit to the addressing socket.
3
Set the required address.
For more detailed information on the AS-Interface and addressing AS-i slaves, please refer
to the operating instructions titled "Addressing and Diagnosis Instrument for AS-i Modules"
(3RK1703-2WB02-1CA1).
Note
The module address can be changed as often as required.