Functions
7.1 Normal switching duty
SIRIUS 3RA6 Compact Starter
System Manual, 02/2008, GWA 4NEB 560 0601-02 DS 02
51
When the actuator is in the READY position, the 3RA62 compact starter reversing starter
can adopt the following statuses:
Table 7-4
Actuator display elements READY (reversing starter)
LEDs
Actuator
ON I 1
ON I 2
A1/A2
B1/B2
Compact starter status
READY
OFF
OFF
OFF
Compact starter is ready:
- The circuit breaker mechanism is on.
- The main contacts are open.
- The control voltage is not present.
READY
GREEN
OFF
GREEN
Compact starter is on:
- The circuit breaker mechanism is on.
- The main contacts for "direction of rotation 1" are
closed.
- The control voltage is present.
READY
OFF
GREEN
GREEN
Compact starter is on:
- The circuit breaker mechanism is on.
- The main contacts for "direction of rotation 2" are
closed.
- The control voltage is present.
READY
OFF
OFF
GREEN
Overload tripped
Actuator TRIPPED
The compact starter has shut down because a malfunction or short circuit has been
detected.
The actual trigger event can be identified by referring to the "RLT 0%" display window.
When the actuator is in the TRIPPED position, the 3RA61compact starter direct starter and
3RA62 compact starter reversing starter can adopt the following statuses:
Table 7-5
Actuator TRIPPED display elements (direct/reversing starter)
Mech. display
Actuator
RLT 0%
Compact starter status
TRIPPED
No display
Short circuit tripped
TRIPPED
White display
Malfunction (e.g. end of service life reached)