Standard mapping 3-1
2-6
SIPROTEC Modbus - Bus mapping 7UM62
C53000-L1840-C009-03
2.2.8
Registers 10037 to 10040: Stator ground fault protection
2.2.9
Registers 10041 to 10042: Stator ground fault protection with 3
rd
harmonic
2.2.10 Registers 10043 to 10046: Overvoltage protection
2.2.11 Registers 10047 to 10050: Undervoltage protection
Register
Designation of the
SIPROTEC objects
Comments
Internal
object no.
10037
59/67 V0 PU
1 = 59N/67GN V0 picked up
5186
10038
59/67 I0 PU
1 = 59N/67GN I0 picked up
5188
10039
59/67 V0 TRIP
1 = 59N/67GN V0 stage TRIP
5187
10040
59N/67GN TRIP
1 = 59N/67GN TRIP
5193
Register
Designation of the
SIPROTEC objects
Comments
Internal
object no.
10041
27TN/59TN PU
1 = 27TN/59TN with 3
rd
harmomic picked up
5567
10042
27TN/59TN TRP
1 = 27TN/59TN with 3
rd
harmomic TRIP
5568
Register
Designation of the
SIPROTEC objects
Comments
Internal
object no.
10043
59-1 picked up
1 = 59-1 Overvoltage V> picked up
6568
10044
59-2 picked up
1 = 59-2 Overvoltage V>> picked up
6571
10045
59-1 TRIP
1 = 59-1 Overvoltage V> TRIP
6570
10046
59-2 TRIP
1 = 59-2 Overvoltage V>> TRIP
6573
Register
Designation of the
SIPROTEC objects
Comments
Internal
object no.
10047
27-1 picked up
1 = 27-1 Undervoltage V< picked up
6533
10048
27-2 picked up
1 = 27-2 Undervoltage V<< picked up
6537
10049
27-1 TRIP
1 = 27-1 Undervoltage V< TRIP
6539
10050
27-2 TRIP
1 = 27-2 Undervoltage V<< TRIP
6540
Содержание SIPROTEC4 7UM62
Страница 6: ...Preface iv SIPROTEC Modbus Bus mapping C53000 L1840 C009 03 ...
Страница 8: ...Revision index vi SIPROTEC Modbus Bus mapping C53000 L1840 C009 03 ...
Страница 12: ...Table of contents x SIPROTEC Modbus Bus mapping C53000 L1840 C009 03 ...
Страница 58: ...Standard mapping 3 2 3 20 SIPROTEC Modbus Bus mapping 7UM62 C53000 L1840 C009 03 ...
Страница 60: ...Glossary 4 2 SIPROTEC Modbus Bus mapping C53000 L1840 C009 03 ...