Standard mapping 3-2
3-19
SIPROTEC Modbus - Bus mapping 7UM62
C53000-L1840-C009-03
3.4.8
Registers 40601 to 40626: Event recorder (Sequence of Events)
•
Registers are write-protected (with the exception of “SOE_Control”).
1
•
Information regarding the individual information in the handshake register, the data
type “Message block” and the evaluation of Event recorder entries you find in the
manual “SIPROTEC Communication module, Modbus - Communication profile”
(ref. to page i).
•
Only the annunciation “Data invalid” (ref. to chap. 3.4.3) is routed per default to the
Event recorder.
Further annunciations can be added to the Event recorder using DIGSI (ref. to chap.
“Customization of the allocations” in the manual “SIPROTEC Communication
module, Modbus - Communication profile”).
1.
A write access is rejected with exception code 03 (ILLEGAL_DATA_VALUE).
Register
Designation
Comments
40601
No. of Event recorder entries
Number of Event recorder entries which still were not read
40602
“SOE_Control”
Handshake register (read/write access)
40603
Message block #1
Register type / Bit offset #1
40604
Register address #1
40605
Message cause / Indication type #1
40606
Value #1
40607
-
40610
Time stamp #1
40611
Message block #2
Register type / Bit offset #2
40612
Register address #2
40613
Message cause / Indication type #2
40614
Value #2
40615
-
40618
Time stamp #2
40619
Message block #3
Register type / Bit offset #3
40620
Register address #3
40621
Message cause / Indication type #3
40622
Value #3
40623
-
40626
Time stamp #3
Содержание SIPROTEC4 7UM62
Страница 6: ...Preface iv SIPROTEC Modbus Bus mapping C53000 L1840 C009 03 ...
Страница 8: ...Revision index vi SIPROTEC Modbus Bus mapping C53000 L1840 C009 03 ...
Страница 12: ...Table of contents x SIPROTEC Modbus Bus mapping C53000 L1840 C009 03 ...
Страница 58: ...Standard mapping 3 2 3 20 SIPROTEC Modbus Bus mapping 7UM62 C53000 L1840 C009 03 ...
Страница 60: ...Glossary 4 2 SIPROTEC Modbus Bus mapping C53000 L1840 C009 03 ...