Standard mapping 3-2
3-12
SIPROTEC Modbus - Bus mapping 7UM62
C53000-L1840-C009-03
3.3
Input registers (3X references)
•
Ref. to chap. 1.2.3 for additional notes regarding scaling of measured values.
Register
Designation of the
SIPROTEC objects
Comments
Scaling
(32767 corresponds to ...)
Internal
object no.
30001
IA S2=
Operat. meas. current A side 2
327.67 %
724
30002
IB S2=
Operat. meas. current B side 2
327.67 %
725
30003
IC S2=
Operat. meas. current C side 2
327.67 %
726
30004
Va-b=
Va-b
327.67 %
624
30005
Vb-c=
Vb-c
327.67 %
625
30006
Vc-a=
Vc-a
327.67 %
626
30007
P =
P (active power)
327.67 %
641
30008
Q =
Q (reactive power)
327.67 %
642
30009
f =
Frequency
327.67 Hz
644
30010
I2 =
I2 (negative sequence)
327.67 %
606
30011
Θ
/
Θ
trip =
Temperature rise for warning and trip
327.67 %
801
30012
<user-defined>
not pre-allocated
-
-
30013
IA S1=
Operat. meas. current A side 1
327.67 %
721
30014
IB S1=
Operat. meas. current B side 1
327.67 %
722
30015
IC S1=
Operat. meas. current C side 1
327.67 %
723
30016
<user-defined>
1
1 Available from version V02.02.01 of Standard mapping 3-2.
not pre-allocated
-
-
30017
<user-defined>
not pre-allocated
-
-
30018
<user-defined>
not pre-allocated
-
-
30019
<user-defined>
not pre-allocated
-
-
30020
<user-defined>
not pre-allocated
-
-
30021
<user-defined>
not pre-allocated
-
-
Содержание SIPROTEC4 7UM62
Страница 6: ...Preface iv SIPROTEC Modbus Bus mapping C53000 L1840 C009 03 ...
Страница 8: ...Revision index vi SIPROTEC Modbus Bus mapping C53000 L1840 C009 03 ...
Страница 12: ...Table of contents x SIPROTEC Modbus Bus mapping C53000 L1840 C009 03 ...
Страница 58: ...Standard mapping 3 2 3 20 SIPROTEC Modbus Bus mapping 7UM62 C53000 L1840 C009 03 ...
Страница 60: ...Glossary 4 2 SIPROTEC Modbus Bus mapping C53000 L1840 C009 03 ...