Functions
2.1 General
SIPROTEC, 6MU805, Manual
C53000-G1140-C380-5, Release date 06.2018
24
Current Clipping Limit Ratio
Address 0
480
ClipC
informs the ratio of the clipping limit of the instantaneous current to the rated primary
voltage multiplied with a square root of two. For example “clip=20” applied with rated primary current of
IP
r
=500A
RMS
means clipping will occur at ±14140A
PEAK.
Primary currents with magnitude above the clipping
limit may saturate analogue circuits and/or digital filters within the instrument transformer resulting in highly in-
accurate sampled values
Voltage Clipping Limit Ratio
Address 0
481
ClipV
informs the ratio of the clipping limit of the instantaneous voltage to the rated primary
voltage multiplied with a square root of two. For example “clip=2” applied with rated primary voltage of UP
r
=5
kV
RMS
means clipping may occur at ±14.14 kV
PEAK
. Primary voltages with magnitude above the clipping limit
may saturate analogue circuits and/or digital filters within the instrument transformer resulting in highly inaccu-
rate sampled values
Nominal Values of Voltage Transformers (VTs) (Only For 1-phase System)
Currently 4 channels voltage are supported. Every channel has its own configuration. Address 0
570, 0572, 0574,
0576
are for Channel Rated Primary Volatge Values, and Address 0
571, 0573, 0575, 0577
are for Channel Rated
Second Voltage Values. At these addresses, information is entered regarding to the primary nominal voltage
and secondary nominal voltage (phase independent) of the connected voltage transformers
2.1.2.3
Settings
The table indicates region-specific default settings.
For clear reference, parameters for 1-phase and 3-phase are listed respectively.
Table 3: Settings for 3-phase Ratio
Addr.
Parameter
Setting Options
Default Setting
Comments
0202
Vnom PRIMARY
0.10 .. 800.00 kV 20.00 kV
Rated Primary Voltage
0203
Vnom
SECONDARY
34 .. 400 V
100 V
Rated Secondary Voltage (L-L)
0204
CT PRIMARY
10 .. 25000 A
400 A
CT Rated Primary Current
0205
CT SECONDARY
1 A
5 A
1 A
CT Rated Secondary Current
0206A Vph/Vdelta
1.00 .. 3.00
1.73
Matching ratio Phase-VT To
Open-Delta-VT
0214
Rated Frequency
50 Hz
60 Hz
50 Hz
Rated Frequency
0217
Ignd-CT PRIM
1 .. 25000 A
400 A
Ignd-CT rated primary current
0218
Ignd-CT SEC
1 A
5 A
1 A
Ignd-CT rated secondary
current
0325
Vnom sec Vx
34 .. 230 V
100 V
Rated Secondary Voltage Vx
0333
Vnom prim Vx
0.10 .. 800.00 kV 20.00 kV
Rated Primary Voltage Vx
0352
U4 inverting
YES
NO
NO
U4 inverting
0369
VT Con Type
Conventional
Conventional
Voltage Connection Type
Содержание SIPROTEC 6MU805
Страница 8: ...Open Source Software SIPROTEC 6MU805 Manual C53000 G1140 C380 5 Release date 06 2018 4 ...
Страница 18: ...Introduction 1 3 Characteristics SIPROTEC 6MU805 Manual C53000 G1140 C380 5 Release date 06 2018 14 ...
Страница 74: ...Functions 2 5 Device Operation SIPROTEC 6MU805 Manual C53000 G1140 C380 5 Release date 06 2018 70 ...
Страница 160: ...Literature SIPROTEC 6MU805 Manual C53000 G1140 C380 5 Release date 06 2018 156 ...
Страница 162: ...Index 158 SIPROTEC 6MU805 Manual C53000 G1140 C380 5 Release date 06 2018 ...