Technical Data
4.1 General Device Data
SIPROTEC, 6MU805, Manual
C53000-G1140-C380-5, Release date 06.2018
108
4.1
General Device Data
4.1.1
Analog Inputs
Current Inputs
Voltage Inputs
Standard:
Nominal frequency
f
Nom
50 Hz
60 Hz
Frequency operating range
GPS MU
49 Hz to 51 Hz
58.5 Hz to 61.5 Hz
PPS MU
40 Hz to 70 Hz (independent of the nominal
frequency)
Nominal current
I
Nom
1 A or 5 A
Consumption per phase and ground path
- for
I
Nom
= 1 A
- for
I
Nom
= 5 A
0.1 VA
0.5 VA
Current overload capability
- thermal (rms)
- dynamic (peak value)
500 A for 1 s
50 A for 10 s
20 A continuous
1250 A (half-cycle)
Standard (applies also to capacitive voltage measurement):
Measuring range
0 V to 250 V
Consumption
at 100 V
approx. 0.005 VA
Voltage overload capability
- thermal (rms)
230 V continuous