Mounting and Commissioning
3.3 Commissioning
SIPROTEC, 6MU805, Manual
C53000-G1140-C380-5, Release date 06.2018
99
3.3.5
Checking the Status of Binary Inputs and Outputs
Prefacing Remarks
The binary inputs, outputs, and LEDs of the 6MU805 can be individually and precisely controlled in DIGSI. This
feature is used to verify control wiring from the device to plant equipment (operational checks) during commis-
sioning. This test option should however definitely not be used while the device is in “real” operation.
DANGER!
Danger evolving from operating the equipment (e.g. circuit breakers, disconnectors) by means of the
test function
Non-observance of the following measure will result in death, severe personal injury or substantial property
damage.
Equipment used to allow switching such as circuit breakers or disconnectors is to be checked only during com-
missioning. Do not under any circumstances check them by means of the test function during real operation by
transmitting or receiving messages via the system interface.
Note
After finishing the hardware tests, the device will reboot. Thereby, all annunciation buffers are erased. If re-
quired, these buffers should be read out with DIGSI and saved prior to the test.
The hardware test can be carried out using DIGSI in the Online operating mode:
• Open the
Online
directory by double-clicking; the operating functions for the device appear.
• Click on
Test
; the function selection appears in the right half of the screen.
• Double-click in the list view on
Hardware Test
. The dialog box of the same name opens (see the following
figure).
Structure of the Test Dialog Box
The dialog box is classified into three groups:
BI
for binary inputs,
REL
for output relays, and
LED
for light-
emitting diodes. On the left of each of these groups is an accordingly labeled button. By double-clicking a
button, information regarding the associated group can be shown or hidden.
In the column
Status
the present (physical) state of the hardware component is displayed. Indication is made
by symbols. The physical actual states of the binary inputs and outputs are indicated by an open or closed
switch symbol, the LEDs by a dark or illuminated LED symbol.
The opposite state of each element is displayed in the column
Scheduled
. The display is made in plain text.
The right-most column indicates the commands or messages that are configured (masked) to the hardware
components.
Содержание SIPROTEC 6MU805
Страница 8: ...Open Source Software SIPROTEC 6MU805 Manual C53000 G1140 C380 5 Release date 06 2018 4 ...
Страница 18: ...Introduction 1 3 Characteristics SIPROTEC 6MU805 Manual C53000 G1140 C380 5 Release date 06 2018 14 ...
Страница 74: ...Functions 2 5 Device Operation SIPROTEC 6MU805 Manual C53000 G1140 C380 5 Release date 06 2018 70 ...
Страница 160: ...Literature SIPROTEC 6MU805 Manual C53000 G1140 C380 5 Release date 06 2018 156 ...
Страница 162: ...Index 158 SIPROTEC 6MU805 Manual C53000 G1140 C380 5 Release date 06 2018 ...