Power output diagnostics
Power output diagnostics
The device features a diagnostics function for detecting power output faults. In every half-
wave, the status of the power output is requested and checked at a fixed point in time.
The following faults are detected:
●
Heating element fault
●
Breakdown of a solid state relay (SSR)
●
Incoming fuse has tripped
●
Outgoing fuse ruptured or SSR has high resistance
Requirements for diagnostics
The "SSR breakdown" fault is always indicated (provided the mains voltage is connected),
regardless of heating status; all other faults are only indicated when heating is enab
led
(heating is "ON").
Diagnostic functions
The faults that can be detected are listed in the table below complete with their error codes:
Fault
Error code
Description / Special characteristics
Heating element fault
1
-
SSR breakdown
2
"Breakdown" means the SSR (solid state relay) is
defective and conducts continuously even without
being activated.
Incoming fuse has tripped
3
-
Outgoing fuse ruptured or
SSR has high resistance
4
This fault can only be detected if the power output
is switched on.
For a 0 % setpoint, the fault is not detected and
also cannot be indicated.
You will find information about the causes of faults and possible rectification measures in the
Fault reporting through diagnostics data section.
Содержание SIPLUS HCS3200
Страница 1: ......
Страница 2: ......
Страница 8: ...Introduction 1 1 Introduction SIPLUS HCS3200 8 Operating Instructions 07 2014 A5E31278506C 002 ...
Страница 12: ...Safety notes 2 2 IT security SIPLUS HCS3200 12 Operating Instructions 07 2014 A5E31278506C 002 ...
Страница 16: ...Description 3 4 System configuration SIPLUS HCS3200 16 Operating Instructions 07 2014 A5E31278506C 002 ...
Страница 24: ...Mounting 5 3 Final work SIPLUS HCS3200 24 Operating Instructions 07 2014 A5E31278506C 002 ...
Страница 44: ...Functions 8 6 Temperature monitoring SIPLUS HCS3200 44 Operating Instructions 07 2014 A5E31278506C 002 ...
Страница 66: ...Technical data 12 2 Dimension drawings SIPLUS HCS3200 66 Operating Instructions 07 2014 A5E31278506C 002 ...
Страница 74: ......