![Siemens SIPLUS HCS3200 Скачать руководство пользователя страница 39](http://html.mh-extra.com/html/siemens/siplus-hcs3200/siplus-hcs3200_operating-instructions-manual_376934039.webp)
SIPLUS HCS3200
Operating Instructions, 07/2014, A5E31278506C/002
39
Functions
8
8.1
Power output control
Power output control
Zero-point switching solid state relays are used for controlling the heating elements. Nine
individually-controllable power outputs are implemented.
They are controlled in half-waves: For each half-wave, the controller supplies On/Off
information to the relay and this switches as specified at the next zero point.
The setpoints for controlling the power outputs lie within a value range of 0 % to 99 %
(reference value: 100 half-waves).
Depending on the specified setpoint, the power outputs are controlled with an equal number
of positive and negative half-waves (reference value: 200 half-waves).
To avoid excessively high inrush currents, the power outputs are switched on time-delayed.
Содержание SIPLUS HCS3200
Страница 1: ......
Страница 2: ......
Страница 8: ...Introduction 1 1 Introduction SIPLUS HCS3200 8 Operating Instructions 07 2014 A5E31278506C 002 ...
Страница 12: ...Safety notes 2 2 IT security SIPLUS HCS3200 12 Operating Instructions 07 2014 A5E31278506C 002 ...
Страница 16: ...Description 3 4 System configuration SIPLUS HCS3200 16 Operating Instructions 07 2014 A5E31278506C 002 ...
Страница 24: ...Mounting 5 3 Final work SIPLUS HCS3200 24 Operating Instructions 07 2014 A5E31278506C 002 ...
Страница 44: ...Functions 8 6 Temperature monitoring SIPLUS HCS3200 44 Operating Instructions 07 2014 A5E31278506C 002 ...
Страница 66: ...Technical data 12 2 Dimension drawings SIPLUS HCS3200 66 Operating Instructions 07 2014 A5E31278506C 002 ...
Страница 74: ......