SIPART PS2 (6DR5...)
A5E03436620-AB, 01/2017
39
Rated conditions
Degree of protection
1)
IP66 to IEC/EN 60529 / NEMA 4X
Mounting position
Any; in wet environment, pneumatic connections and
outlet opening not upward
Vibration resistance
•
Harmonic oscillations (sine) according to EN 60068-2-
6/10.2008
3.5 mm (0.14"), 2 ... 27 Hz, 3 cycles/axle
98.1 m/s² (321.84 ft/s²), 27 ... 300 Hz, 3 cycles/axle
•
Bumping (half-sine) according to EN 60068-2-27/02.2010 150 m/s² (492 ft/s²), 6 ms, 1000 shocks/axle
•
Noise (digitally controlled) according to EN 60068-2-
64/04.2009
10 ... 200 Hz; 1 (m/s²)²/Hz (3.28 (ft/s²)²/Hz)
200 ... 500 Hz; 0.3 (m/s²)²/Hz (0.98 (ft/s²)²/Hz)
4 hours/axle
•
Recommended range of continuous operation of the entire
control valve
≤
30 m/s² (98.4 ft/s²) without resonance peak
Climate class
According to IEC/EN 60721-3
•
Storage
1K5, but -40 ... +80°C (1K5, but -40 ... +176°F)
•
Transport
2K4, but -40 ... +80°C (2K4, but -40 ... +176°F)
1)
Max. impact energy 1 Joule for enclosure with inspection window 6DR5..0 and 6DR5..1 or max. 2 Joule for 6DR5..3
2)
At ≤
-
10 °C (≤ 14 °F) the display refresh rate of the indicator is limited. When using position feedback module, only T4 is
permissible.
3)
The following applies to order suffix (order code) -Z M40: -40 ... +80 °C (-40 ... +176°F)
7.1.2
Pneumatic data
Pneumatic data
Auxiliary power (air supply)
Compressed air, carbon dioxide (CO2), nitrogen (N), noble
gases or cleaned natural gas
•
Pressure
1)
1.4 ... 7 bar (20.3 to 101.5 psi)
Air quality to ISO 8573-1
•
Solid particulate size and density
Class 2
•
Pressure dew point
Class 2 (min. 20 K (36°F) below ambient temperature)
•
Oil content
Class 2
Unrestricted flow (DIN 1945)
•
Inlet air valve (ventilate actuator)
2)
2 bar (29 psi)
4.1 Nm³/h (18.1 USgpm)
4 bar (58 psi)
7.1 Nm³/h (31.3 USgpm)
6 bar (87 psi)
9.8 Nm³/h (43.1 USgpm)
•
Exhaust valve (deaerate actuator for all versions except
fail in place)
2)
2 bar (29 psi)
8.2 Nm³/h (36.1 USgpm)
4 bar (58 psi)
13.7 Nm³/h (60.3 USgpm)
6 bar (87 psi)
19.2 Nm³/h (84.5 USgpm)
•
Exhaust valve (deaerate actuator for fail in place version)
2 bar (29 psi)
4.3 Nm³/h (19.0 USgpm)
4 bar (58 psi)
7.3 Nm³/h (32.2 USgpm)
6 bar (87 psi)
9.8 Nm³/h (43.3 USgpm)
Valve leakage
< 6
⋅
10
-4
Nm³/h (0.0026 USgpm)
Throttle ratio
Adjustable up to ∞: 1
Auxiliary power consumption in the controlled state
<
3.6⋅10
-2
Nm³/h (0.158 USgpm)