4.2.6.2
M12 connector in basic device SIPART PS2 with PROFIBUS PA
You have a positioner 6DR55..-0.R.. or 6DR55..-0.S. In this case the M12 connector is connected to the bus circuit of the
basic electronics.
Table 4-2
Assignment diagram
Bus circuit terminal
Pole designation
7
1 - Brown
Shield support of housing
4 - Black
6
3 - Blue
4.2.6.3
M12 connector in basic device SIPART PS2 with FOUNDATION Fieldbus
You have a positioner 6DR56..-0.R.. or 6DR56..-0.S.. In this case the M12 connector is connected to the bus circuit of the
basic electronics.
Table 4-3
Assignment diagram
Bus circuit terminal
Pole designation
7
1 - Brown
Shield support of housing
4 - Black
6
3 - Blue
4.2.6.4
M12 connector for connection of the outputs of the alarm module 6DR4004-6A / -8A (-Z
D55)
You have a positioner with order suffix -Z order code D55. In this version of the positioner, the M12 connector is used to
electrically connect the current output of the position feedback module.
Table 4-4
Assignment diagram
Alarm output terminal
Pole designation
41 (+)
1 - Brown
52 (-)
4 - Black
42 (-)
3 - Blue
51 (+)
2 - White
4.2.6.5
M12 connector for connecting the outputs of the position feedback module 6DR4004-6J /
8J (-Z D53)
You have a positioner with order suffix -Z order code D53. In this version of the positioner, the M12 connector is used to
electrically connect the current output of the position feedback module.
Table 4-5
Assignment diagram
Current output terminal
Pole designation
61 (+)
1 - Brown
Shield support of housing
4 - Black
62 (-)
3 - Blue
4.2.6.6
M12 connector for connecting the external position detection system (-Z D54)
You have a positioner with order suffix -Z order code D54. In this version of the positioner, the M12 connector is used to
electrically connect the fitted EMC filter module (C73451-A430-D23). Connect the external position detection system using