SIPART PS2 (6DR5...)
A5E03436620-AB, 01/2017
25
Table 4-6
Assignment diagram
Terminal
Pole designation
POS (X1/2)
3 - Blue
VCC (X1/4)
1 - Brown
GND (X1/1)
4 - Black
VREF (X1/3)
2 - White
4.2.6.7
M12 connector for connecting the outputs of the SIA module 6DR4004-6G /-8G (-Z D56)
You have a positioner with order suffix -Z order code D56. In this version of the positioner, the M12 connector is used to
electrically connect the outputs of the SIA module.
Table 4-7
Assignment diagram
Alarm output terminal
Pole designation
41 (+)
1 - Brown
52 (-)
4 - Black
42 (-)
3 - Blue
51 (+)
2 - White
4.3
Pneumatic connection
WARNING
Pneumatic auxiliary power
Owing to safety reasons, the pneumatic auxiliary power supply must be fed after installation only if the positioner is
switched to the "P-manual mode" when an electrical signal is available, refer to the as-delivered condition.
Note
Specifications regarding air quality
Observe the specifications regarding the air quality, see section "Technical specifications > Pneumatic data (Page 39)".
●
If required, connect the pressure gauge block for supply air and actuating pressure.
●
Connection via female thread G¼ or ¼" NPT:
–
Y1: actuating pressure 1 for single and double-acting actuators
–
Y2: actuating pressure 2 for double-acting actuators
–
Exhaust air outlet with a sound absorber. Remove the sound absorber if required.
●
For double-acting actuators, connect actuating pressure Y1 or Y2 depending on the desired safety setting.
●
Safety position in case of electrical auxiliary power supply failure:
–
Positioner with single-acting pneumatic system: Y1 depressurized
–
Positioner with double-acting pneumatic system: Y1 pressurized (maximum actuating pressure), Y2 depressurized
–
Positioner with Fail in Place pneumatic system: Hold Y1 and Y2 (current actuating pressure)