Installation & Operating Manual 

 

IOM-SX_SH01-01 

SX 

SH 

 

                  IOM-SX_SH01-01  

 

Page 1 / 2 

 

 

READ THIS INSTRUCTION FIRST 
To avoid serious or fatal personal injury or major property damage, read and follow all safety instruction in this manual.  
If you require additional assistance, please contact SOLDO.

 

 
SAVE THIS INSTRUCTION 

Declaration of conformity as defined by the 

ATEX directive 94/9/EC

Doc.: CE001-06

Herewith we declare that the  SOLDO “limit switch box SX series”,  

 

  II 2 G Ex d IIB T6/T5/ T4 

 

  II 2 D Ex tD B21 T85°C/T100°C/T135°C 

and the SOLDO “limit switch box SH series”,  

 

  II 2 G Ex d IIB+H2 T6/T5/ T4 

 

  II 2 D Ex tD B21 T85°C/T100°C/T135°C 

are in conformity with the provision of the ATEX directive 94/9/EC “Equipment or Protective 
Systems intended for use in potentially explosive atmospheres”  and with national 
implementing legislation and that appropriate harmonized standards have been applied: 
EN 60079-0 : 2006  EN 60079-1 : 2007  EN 61241-0 : 2006  EN 61241-1 : 2004 

Directive 89/336/CEE Electromagnetic compatibility.  

EN 61326-1:2006 

Directive  73/23/CEE Low tension  

EN 60529:1991   EN 60730-1:2000 

EC- Type examination certificate  
ATEX:

 ITS 09ATEX 16281X                      

IECEx:

 IECEx ITS 09.0020X 

Production quality assurance notification

ATEX:

 ITS 08ATEXQ5820                         

IECEx:

 GB/ITS/QAR09.0004/00 

 

WARNING!

 

 

Warns of hazard that MAY cause serious personal injury, death or major property damage. 

HAZARDOUS VOLTAGE. Disconnect all power before servicing equipment.  
DO NOT REMOVE COVER WHEN ENERGISED. 

CAUTION ! 

 

Do not exceed the limit switch performance limitation. Exceeding the limitation may cause damage to the limit 
switch, actuator and valve.  
The conduit plug supplied with the switch boxes are for transit purposes only. IP67 protection depends on 
cable gland and cabling methods used. Limit switchbox for quarter-turn valve device (90° rotation). 
Maximum shaft angular velocity 250 rpm.  
Follow switch adjustment & indicator setting before servicing the limit switch box.  

1 INSTALLATION 

1.1  Attach proper mounting bracket (1) to the box (4) housing using four M 6X8 bolts (2). 
1.2  Align shaft (5) to  actuator shaft and engage it. 
1.3  Attach bracket to actuator using hardware provided (3). 
 

2 SWITCH 

ADJUSTMENT 

 

2.1  Loose the screws (8) and remove box cover (7). 
2.2  Follows indication in “Cams setting” Page 2. 
2.3  Box with 3-4 switches, set the actuator in the extra position you have to signal. Act according to indications 

in “Cams setting ” to set cams of the switch number 3 and 4. 

2.4  Replace box cover (7). WARNINGS: check seal (6) is properly fitted in slot. Turn manually cover’s shaft (15) 

cheeking to align it to switch box shaft and engage it. Tightening screws (8). 

 

GB 

For other languages visit WWW.SOLDO.NET 

IT 

Per altre lingue visitare il sito WWW.SOLDO.NET 

FR 

Pour les autres langues visite WWW.SOLDO.NET 

DE 

Für andere Sprachen besuchen WWW.SOLDO.NET 

ES 

Para otros idiomas, visite WWW.SOLDO.NET 

Safety instruction to hazardous area installation

Doc.: SI001-03

Model numbers covered SX_ _ _ _ _-_ or SH _ _ _ _ _-_ ( _ indicates options in switches, 
switches quantity, terminal strip, colour, cable entries). The following instructions applies to 
equipment covered by ATEX certificate number: ITS 09ATEX 1

6

281X 

And by IECEX certificate number:  IECEx ITS 09.0020X 
SX limit switch boxes may be used in an hazardous area with flammable gases, vapours and 
powder, group IIB with the following temperature classes: 

T6: -25°C 

 T amb. 

 + 60° C 

Surface temperature T 85°C 

T5: -25°C 

 T amb. 

 + 75° C 

Surface temperature T 100°C 

T4: -25°C 

 T amb. 

 + 105° C  Surface temperature T 135°C 

Special options for -40°C  
defined by “LT1” at the 
 end of the switch box code  

SH limit switch boxes may be used in an hazardous area with flammable gases, vapours and 
powder, group IIB+H2 with the following temperature classes: 

T6: -25°C 

 T amb. 

 + 60° C 

Surface temperature T 85°C 

T5: -25°C 

 T amb. 

 + 75° C 

Surface temperature T 100°C 

T4: -25°C 

 T amb. 

 + 105° C  Surface temperature T 135°C 

Suitably trained personnel shall carry out installation in accordance with applicable code of 
practice 
The user should not repair this equipment. 
The user should provide suitable systems to limit heating coming from valve; max ambient 
temp 105°C 
If the equipment is likely to come into contact with aggressive substances, it is responsibility of 
the user to take suitable precautions that prevent it from being adversely affected, thus 
ensuring that the type of protection is not compromised. Agressive substances – es. Acidic 
liquids or gases that may attack metal . 
The following precautions must be observed: 
i The metallic alloy used for the enclosure, in the event of a rare accident, could cause ignition 
sources due to impact or friction (sparks may occur). This shall be considered when the box is 
installed in group II category 2G areas. 
ii Due to electrostatic charge of plastic pieces, the limit switch box shell only be cleaned with a 
damp cloth.

  

NOMENCLATURE 

SX 
SH 

01  2  0  0 - 1

-

Extra digit 

 

 

 

 

 

 

 

 

 

 To 

define 

special option

 

   

   

 

 

 

 

    Cable entry 

 

 

   

   

 

 

 Colour 

 

 

 

   

   

 

 

Terminal strip  

 

 

   

 Switch 

quantity 

 

 

 

 

Switch type

 

 

 