NOTICE
Freezing of the exhaust air outlets
The exhaust air outlets
②
can ice up. The function of the device is impaired.
• Do not install the positioner with the base plate
①
pointing up.
①
Base plate
②
Exhaust air outlets
Figure 4-1
Exhaust air outlets, base plate
4.2
Mounting to linear actuator
Requirements
Depending on the stroke height, you will need the following mounting kit:
• 3 to 35 mm mounting kit 6DR4004-8V
• 35 to 130 mm mounting kit 6DR4004-8V and additional 6DR4004-8L
Procedure
Sr. no.
*)
Quan‐
tity
Name
Note
6DR4004-8L:
①
1
Lever
For the range of stroke from 10 to 130 mm
6DR4004-8V:
①
1
NAMUR mounting bracket
IEC 60534
Standardized connection point for mount with fin, column or plane surface
②
1
Pick-up bracket
Guides the pulley with the carrier pin and rotates the lever arm.
③
2
Clamping piece
Installs the pick-up bracket on the actuator spindle
④
1
Carrier pin
Installation with pulley
⑤
on lever
⑥
Installing/mounting
4.2 Mounting to linear actuator
SIPART PS100
Compact Operating Instructions, 05/2021, A5E50188940-AA
17