CAUTION
Adhere to the following instructions before working on the control valve and when
attaching the positioner
Danger of injury.
• Prior to working on the control valve, you must move the actuator and the process valve into
a completely pressureless state. Proceed as follows:
– Depressurize the actuator chambers.
– Switch off the supply pressure PZ.
– Secure the process valve.
• Make sure that the actuator has reached the pressureless state.
• If you interrupt the supply pressure PZ to the positioner, the pressureless position can only
be reached after a certain waiting time.
• When mounting, adhere strictly to the following order to avoid injuries or mechanical
damage to the positioner/mounting kit:
– Mount the positioner mechanically.
– Electric connection.
– Connect supply pressure PZ.
– Commission the positioner.
NOTICE
Torque with NPT screwed gland
Device damage. The maximum torque of the cable gland must not be exceeded.
• To avoid damage to the device, the NPT adapter must be held in place while the NPT gland
is screwed into the NPT adapter. Refer to the section "Technical specifications > Mechanical
construction (Page 45)" for the torque value.
4.1.1
Proper mounting
NOTICE
Incorrect mounting
The device can be damaged, destroyed, or its functionality impaired through improper
mounting.
• Before installing ensure there is no visible damage to the device.
• Make sure that process connectors are clean, and suitable gaskets and glands are used.
• Mount the device using suitable tools. Refer to the information in Technical specifications
(Page 43).
Installing/mounting
4.1 Basic safety notes
SIPART PS100
16
Compact Operating Instructions, 05/2021, A5E50188940-AA
Содержание SIPART PS100
Страница 14: ...Safety notes 3 2 Use in hazardous areas SIPART PS100 14 Compact Operating Instructions 05 2021 A5E50188940 AA ...
Страница 32: ...Connecting 5 4 Pneumatic connection SIPART PS100 32 Compact Operating Instructions 05 2021 A5E50188940 AA ...
Страница 42: ...Service and maintenance 8 5 Disposal SIPART PS100 42 Compact Operating Instructions 05 2021 A5E50188940 AA ...