51 | 152
5.3.3 Technical data
FDnet operating voltage
DC 12…33 V
Operating current (quiescent)
180 µA
Operating temperature
-25…+70°C
Storage temperature
-30…+75°C
Air humidity
≤
95 % rel.
Communication protocol
FDnet
Connection terminals
0.28…1.5 mm
2
Color
~RAL 3000, flame red
Design according to EN 54-11
Direct activation 'type A'
Environmental category according
to EN 54-11:
●
FDM225-xx: In buildings
●
FDM226-xx: In buildings and outdoor areas
Color
~RAL 3000, flame red
Protection category (IEC 60529):
●
FDM225-xx: IP44
●
FDM226-xx: IP66
Approvals:
FDM225-RP
FDM225-RP (F)
FDM225-RG
FDM225-RG (F)
FDM226-RP
FDM226-RG
●
VdS
G207092
G207092
G209194
G209194
●
LPCB
126ap/01
126ap/10
126ap/02
126ap/11
126ap/03
126ap/04
●
DNV GL (marine)
-
-
MEDB00003UM
-
System compatibility:
●
FDnet: FS20, AlgoRex, SIGMASYS
●
C-NET: FS720