![Siemens Sinteso FD20 Скачать руководство пользователя страница 123](http://html.mh-extra.com/html/siemens/sinteso-fd20/sinteso-fd20_product-data_383408123.webp)
Special detectors
Manual call point FDM223-Ex
10
008164_y_en_--
123 | 152
10.7.3 Technical data
FDM223-Ex
Operating voltage
DC 13…28 V
Operating current (quiescent)
200
μ
A
Operating temperature
-25…+70 °C
Storage temperature
-35…+75 °C
Air humidity
≤
95 % rel.
Communication protocol
FDnet-Ex
Conductor cross section
1…1.5 mm
2
Color
~RAL 3000 flame red
Protection category (IEC/EN 60529)
●
With seal DMZ1197-AD
IP44
IP66
Ex classification
IECEx
Directive 2014/34/EU:
(ATEX directive)
Ex ia IIC T4 Ga, Ta = -35…70 °C
Ex ia IIIB T135 °C Da , Ta = -35…70 °C
II 1 G Ex ia IIC T4 Ga, Ta = -35…70 °C
II 1 D Ex ia IIIB T135 °C Da, Ta = -35…70 °C
Standards
EN 54-11 Type B (indirect activation)
Standards for explosion-hazard areas
EN 60079-0
EN 60079-11
Ex approvals
●
EC-type examination certificate
●
IECEx
BVS 12 ATEX E 095 X
IECEx BVS 12.0082X
Approvals
●
VdS
●
DNV GL (marine)
G213107
MEDB00003UM
System compatibility
●
FDnet
●
C-NET
FS20, AlgoRex, SIGMASYS
FS720