Automatic fire detectors
Point detector FDOOT241-9, FDOOT241-A, FDO241, FDT241
2
18 | 152
008164_y_en_--
2.3.2.1 Accessories
You will find more information about detector bases and accessories in document
007775.
Addressable detector base FDB221 / FDB221-AA
Function:
●
Detector base with stilts for fire detectors with addressable signal processing
●
'Orange' connection terminals, 0.2…1.5 mm
2
conductor cross-section
●
FDB221-AA also contains micro terminal DBZ1190-AA
Use:
●
For recess-mounted cable entry
●
For surface-mounted cable entry up to a cable diameter of 6 mm
Flat, addressable detector base FDB222
Function:
●
Flat detector base for fire detectors with addressable signal processing
●
'Orange' connection terminals, 0.2…1.5 mm
2
conductor cross-section
Use:
●
For flush mounting; only for recess-mounted cable entry
Base attachment FDB291
Function:
●
For routing surface-mounted cables larger than Ø 6 mm
●
Detector base is secured with a snap fastener
Base attachment humid FDB293
●
For achieving a higher protection category
●
For mounting in wet or humid environments
●
Required when using detector heating unit FDBH291
●
Required when using protective cage DBZ1194 or EMC-protective cage
FDBZ294
●
Mounted between detector base and ceiling
●
Detector base mounted quickly: The detector base simply clicks into place in
base attachment humid FDB293.