Detector base and base attachment
Detector base FDB201, FDB202, FDB221, FDB222
3
008164_y_en_--
25 | 152
1 Detector base FDB2xx / FDB2x1-AA
2 Micro terminal DBZ1190-AA
3 Connection terminal DBZ1190-AB
Sealing element FDBZ295
Function:
●
For improving the protection category. However, detectors can no longer be
installed or removed using the detector exchanger.
Note: Cannot be used in conjunction with designation plate FDBZ291!
Designation plate FDBZ291
●
For labeling with the location address
●
Can only be used without sealing element FDBZ295
Designation plate DBZ1193A
●
For labeling with the location address
●
Can only be used with base attachment wet FDB295 or base attachment
humid FDB293
Detector heating unit FDBH291
●
For operating point detectors in critical ambient conditions during icy
conditions or when there is a danger of moisture condensation. Examples of
application: Cold stores, attics, loading ramps, cheese cellars
●
Optimum function is only guaranteed in conjunction with base attachment wet
FDB295 or base attachment humid FDB293.
●
The point detector temperature increases by approximately 2 °C over the
operating temperature and thus avoids moisture condensation on the detector.
●
Mounted quickly: The detector heating unit clicks into place in the detector
base.