X35
Closed-loop control interface
X36
Closed-loop control interface
Connector assignment
Table 3-1
Connector -X231
Pin
Signal type
Signal designa‐
tion
Signal direction Measuring
sockets
Control signals
closed-loop
control
PADU8 (option
G66)
1
1M24
-X32:8
2
DO_3
Binary signal 3 →
-X32:7
3
DO_2
Binary signal 2 →
-X32:5
4
1M24
-X32:6
5
1M24
-X32:4
6
DO_1
Binary signal 1 →
-X32:3
7
DO_0
Binary signal 0 →
-X32:1
8
1M24
-X32:2
9
1M24
-X31:8
-X1:8
10
AO_3
Analog signal 3 →
-X23
-X31:7
-X1:7
11
AO_2
Analog signal 2 →
-X22
-X31:5
-X1:5
12
1M24
-X31:6
-X1:6
13
1M24
-X31:4
-X1:4
14
AO_1
Analog signal 1 →
-X21
-X31:3
-X1:3
15
AO_0
Analog signal 0 →
-X20
-X31:1
-X1:1
16
1M24
-X31:2
-X1:2
Signals DO_0 to DO_3 of connector -X32 are identical to signals DI_0 to DI_3 of connector -X231, which are supplied from
the PSA. An LED signals the logic state of the respective signals. These signals are not wired to the PADU8 interface.
The eight digital outputs of the PSA are used internally and are therefore preassigned, so not configurable. The eight analog
outputs of the PSA are freely parameterizable and can be used for commissioning and service purposes with the aid of the
starter. Follow the description in the Sinamics List Manual to parameterize the system.
Note
Preassignment of the analog outputs of the PSA
If the converter has optional door indicating devices, analog outputs AO_0 to AO_3 of the PSA
are preassigned.
Description
3.5 Description of the components
SINAMICS SM150 6SL3845-7NN46-7AA0
Operating Instructions 04/2017
45
Содержание SINAMICS SM150
Страница 2: ...20 04 2017 13 53 V27 00 ...
Страница 14: ...Table of contents SINAMICS SM150 6SL3845 7NN46 7AA0 14 Operating Instructions 04 2017 ...
Страница 16: ...Introduction 1 1 About these instructions SINAMICS SM150 6SL3845 7NN46 7AA0 16 Operating Instructions 04 2017 ...
Страница 82: ...Description 3 6 Description of options SINAMICS SM150 6SL3845 7NN46 7AA0 82 Operating Instructions 04 2017 ...
Страница 106: ...Installation 5 9 Connecting the water circuits SINAMICS SM150 6SL3845 7NN46 7AA0 106 Operating Instructions 04 2017 ...
Страница 120: ...Electrical connection 6 5 Connection SINAMICS SM150 6SL3845 7NN46 7AA0 120 Operating Instructions 04 2017 ...
Страница 122: ...Start up SINAMICS SM150 6SL3845 7NN46 7AA0 122 Operating Instructions 04 2017 ...
Страница 190: ...Maintenance 9 7 Repairs SINAMICS SM150 6SL3845 7NN46 7AA0 190 Operating Instructions 04 2017 ...
Страница 192: ...Spare parts SINAMICS SM150 6SL3845 7NN46 7AA0 192 Operating Instructions 04 2017 ...
Страница 196: ...Service Support SINAMICS SM150 6SL3845 7NN46 7AA0 196 Operating Instructions 04 2017 ...
Страница 217: ......