Note
To ensure trouble-free operation without interference or disturbances, route the power cables
and signal lines separately. Interference, for example, will result in the device not behaving as
expected.
When connecting and routing power and signal cables, observe the instructions contained in
the "Electromagnetic compatibility" section.
See also
Electromagnetic compatibility (Page 109)
6.2
Electromagnetic compatibility
The following fundamental information and guidelines facilitate compliance with the EMC
directives.
Note
We recommend that EMC is planned for the entire plant.
Cabinet installation
● Connect painted or anodized metal components using contact washers or remove the
insulating layer.
● Use unpainted, de-oiled mounting plates.
● Establish a central connection between ground and the protective conductor system (PE
protective conductor).
Cable installation
● Cables that are subject to or sensitive to interference should be laid as far apart from each
other as possible.
● The distance between the electric power cable and signal cable should be > 20 cm. The
converter-specific information applies to power cables. You can find further information on
power cables under "Connecting power cables".
● When the cables are routed close to ground potential, the immunity to interference is
increased. For this reason, you are advised to lay these cables along edges and at ground
potential.
● Ground the reserve cores on at least one end.
Electrical connection
6.2 Electromagnetic compatibility
SINAMICS SM150 6SL3845-7NN46-7AA0
Operating Instructions 04/2017
109
Содержание SINAMICS SM150
Страница 2: ...20 04 2017 13 53 V27 00 ...
Страница 14: ...Table of contents SINAMICS SM150 6SL3845 7NN46 7AA0 14 Operating Instructions 04 2017 ...
Страница 16: ...Introduction 1 1 About these instructions SINAMICS SM150 6SL3845 7NN46 7AA0 16 Operating Instructions 04 2017 ...
Страница 82: ...Description 3 6 Description of options SINAMICS SM150 6SL3845 7NN46 7AA0 82 Operating Instructions 04 2017 ...
Страница 106: ...Installation 5 9 Connecting the water circuits SINAMICS SM150 6SL3845 7NN46 7AA0 106 Operating Instructions 04 2017 ...
Страница 120: ...Electrical connection 6 5 Connection SINAMICS SM150 6SL3845 7NN46 7AA0 120 Operating Instructions 04 2017 ...
Страница 122: ...Start up SINAMICS SM150 6SL3845 7NN46 7AA0 122 Operating Instructions 04 2017 ...
Страница 190: ...Maintenance 9 7 Repairs SINAMICS SM150 6SL3845 7NN46 7AA0 190 Operating Instructions 04 2017 ...
Страница 192: ...Spare parts SINAMICS SM150 6SL3845 7NN46 7AA0 192 Operating Instructions 04 2017 ...
Страница 196: ...Service Support SINAMICS SM150 6SL3845 7NN46 7AA0 196 Operating Instructions 04 2017 ...
Страница 217: ......