WARNING
Short-circuits
Damaged cables, or their improper routing, can cause damage to property and personal
injury.
● Only use cables that are completely intact and not damaged. Correctly route the cables.
Do not interchange input and output terminals.
● Make sure that a short-circuit cannot occur on the power cables due to failure of the
insulation as a result of incorrect cable installation.
● Check the electrical connections after service work.
NOTICE
Using magnetizable parts
The use of magnetizable parts, e.g. ferrous cable clamps, is not permitted. The use of
magnetizable parts can damage the converter.
Only use parts that consist of non-magnetic material.
NOTICE
Improper shrinking of cable terminations
If you are connecting the mains and motor-side power cables, when shrinking the cable
terminations, other control lines and fiber-optic cables in the surrounding cable channels can
become damaged.
When shrinking, ensure not to damage cables in the surrounding cable channels.
NOTICE
Incorrectly opening the doors
If you incorrectly open the doors, then this can damage the locking mechanism.
Open the doors as described in Section "Preparing for use".
Note
Control and signal lines must always be connected according to the circuit diagrams supplied
with the unit. Detailed information about connecting the components is given in the
interconnection diagram.
Note
We recommend using shielded cables. Unshielded cables can transfer disturbances to the
control and signal lines and lead to malfunctions in the drive.
Electrical connection
6.1 Safety instructions for electrical connections
SINAMICS SM150 6SL3845-7NN46-7AA0
108
Operating Instructions 04/2017
Содержание SINAMICS SM150
Страница 2: ...20 04 2017 13 53 V27 00 ...
Страница 14: ...Table of contents SINAMICS SM150 6SL3845 7NN46 7AA0 14 Operating Instructions 04 2017 ...
Страница 16: ...Introduction 1 1 About these instructions SINAMICS SM150 6SL3845 7NN46 7AA0 16 Operating Instructions 04 2017 ...
Страница 82: ...Description 3 6 Description of options SINAMICS SM150 6SL3845 7NN46 7AA0 82 Operating Instructions 04 2017 ...
Страница 106: ...Installation 5 9 Connecting the water circuits SINAMICS SM150 6SL3845 7NN46 7AA0 106 Operating Instructions 04 2017 ...
Страница 120: ...Electrical connection 6 5 Connection SINAMICS SM150 6SL3845 7NN46 7AA0 120 Operating Instructions 04 2017 ...
Страница 122: ...Start up SINAMICS SM150 6SL3845 7NN46 7AA0 122 Operating Instructions 04 2017 ...
Страница 190: ...Maintenance 9 7 Repairs SINAMICS SM150 6SL3845 7NN46 7AA0 190 Operating Instructions 04 2017 ...
Страница 192: ...Spare parts SINAMICS SM150 6SL3845 7NN46 7AA0 192 Operating Instructions 04 2017 ...
Страница 196: ...Service Support SINAMICS SM150 6SL3845 7NN46 7AA0 196 Operating Instructions 04 2017 ...
Страница 217: ......