Parameter
Setting
p1075
Supplementary setpoint
p1076
Supplementary setpoint scaling
r1077
Supplementary setpoint effective
r1078
Total setpoint effective
These parameters concern connector inputs to which the setpoint values are connected.
Function diagram
FP 3030
Skip frequency bands and minimum speed
Variable-speed drives can generate critical whirling speeds within the control range of the
entire drive train. This prevents steady-state operation in their proximity, that is,
the range of critical whirling speeds can still be passed through. The drive, however, must not
remain here because this can cause excitation of the sympathetic oscillations.
The suppression bandwidths allow this range to be blocked for steady-state operation.
Because the points at which critical whirling speeds occur in a drive train can vary depending
on age or thermal factors, a broader control range should be blocked. To ensure that the speed
does not constantly increase and decrease in the suppression bandwidth (speeds), the bands
are assigned a hysteresis.
Specify a minimum speed in order to block a specific range around the stopped state for
stationary operation.
Table 8-1
Parameter
Parameter
Setting
p1091
Suppression speed 1
p1092
Suppression speed 2
p1093
Suppression speed 3
p1094
Suppression speed 4
p1101
Suppression speed bandwidth
p1080
Minimum speed
r1112
Speed setpoint after minimum limiting
You can find additional information in function diagrams 1550 and 3050.
Operation
8.4 Functions
SINAMICS SM150 6SL3845-7NN46-7AA0
128
Operating Instructions 04/2017
Содержание SINAMICS SM150
Страница 2: ...20 04 2017 13 53 V27 00 ...
Страница 14: ...Table of contents SINAMICS SM150 6SL3845 7NN46 7AA0 14 Operating Instructions 04 2017 ...
Страница 16: ...Introduction 1 1 About these instructions SINAMICS SM150 6SL3845 7NN46 7AA0 16 Operating Instructions 04 2017 ...
Страница 82: ...Description 3 6 Description of options SINAMICS SM150 6SL3845 7NN46 7AA0 82 Operating Instructions 04 2017 ...
Страница 106: ...Installation 5 9 Connecting the water circuits SINAMICS SM150 6SL3845 7NN46 7AA0 106 Operating Instructions 04 2017 ...
Страница 120: ...Electrical connection 6 5 Connection SINAMICS SM150 6SL3845 7NN46 7AA0 120 Operating Instructions 04 2017 ...
Страница 122: ...Start up SINAMICS SM150 6SL3845 7NN46 7AA0 122 Operating Instructions 04 2017 ...
Страница 190: ...Maintenance 9 7 Repairs SINAMICS SM150 6SL3845 7NN46 7AA0 190 Operating Instructions 04 2017 ...
Страница 192: ...Spare parts SINAMICS SM150 6SL3845 7NN46 7AA0 192 Operating Instructions 04 2017 ...
Страница 196: ...Service Support SINAMICS SM150 6SL3845 7NN46 7AA0 196 Operating Instructions 04 2017 ...
Страница 217: ......