Note
The fiber-optic cables for the gating boards must be properly inserted in the connectors.
9.4.5
Replacing filter mats
NOTICE
Damage due to dust deposits
Dust can enter the interior of the cabinet during filter mat replacement due to the suction of the
running cabinet fans. Dust deposits can damage the device.
● Ensure that no dust enters the cabinet when replacing the filter mats.
1. Remove the screws for the louvered fan grid in the cabinet door.
Figure 9-5
Example diagram: Replacing filter mats
2. Remove the filter mat.
3. If there is a slight amount of dirt, clean the filter mat at a suitable location. Depending on the
degree of pollution, you can also clean the filter mats using a vacuum cleaner. If the filter mat
is damaged, or the frequency of alarms increases, dispose of the dirty filter mat in the correct
fashion. Use a new filter mat.
4. Insert the filter mat in the frame of the fan opening. In order that dirt is not drawn in, insert
a clean mat in the same direction as it was installed before the cleaning.
5. Carefully place the louvered cover over the frame.
6. Retighten the cover screws.
Maintenance
9.4 Inspection and maintenance
SINAMICS SM150 6SL3810-7NN38-0AA1
152
Operating Instructions Rev.201910281406 EXAMPLE
Содержание SINAMICS SM150 6SL3810-7NN38-0AA1
Страница 2: ...28 10 2019 14 06 V32 00 ...
Страница 12: ...Table of contents SINAMICS SM150 6SL3810 7NN38 0AA1 12 Operating Instructions Rev 201910281406 EXAMPLE ...
Страница 106: ...Start up SINAMICS SM150 6SL3810 7NN38 0AA1 106 Operating Instructions Rev 201910281406 EXAMPLE ...
Страница 168: ...Spare parts SINAMICS SM150 6SL3810 7NN38 0AA1 168 Operating Instructions Rev 201910281406 EXAMPLE ...
Страница 172: ...Service Support SINAMICS SM150 6SL3810 7NN38 0AA1 172 Operating Instructions Rev 201910281406 EXAMPLE ...
Страница 183: ......
Страница 186: ......
Страница 188: ......