3.6.19
Safety locking system (option M10)
The safety locking system is based on the key transfer system developed by Castell. It is a
supplementary mechanism to the electromechanical door locking system integrated as
standard. The medium-voltage breaker must be opened before access can be gained to the
coded key of the key exchange unit. The opened medium-voltage breaker releases the key to
the key exchange unit. This key enables the access to the keys for the cabinet doors of the
power unit. This key interlocking system ensures that the converter is disconnected from the
medium-voltage supply and that no cabinet components are connected to medium voltage. As
long as the cabinet doors are not closed again and the keys to the power-unit cabinet are not
inserted back in the key exchange unit, the key for the medium-voltage breaker will not be
released. The medium-voltage breaker cannot be switched on again.
See also
Secure locking system (option M10) (Page 147)
3.6.20
Dust protection (option M11)
This option equips the cabinet doors with additional filter mats. The filter mats prevent the entry
of dangerous dust deposits on the power module components.
The filter mats are fitted to the exterior of the cabinet doors, which means that they can be
replaced during operation.
The degree to which the filter mats are contaminated is constantly monitored by a differential
pressure system. A message is output in good time prompting the operator to service the filter
mats before they become blocked.
3.6.21
Signal and control cable (max. 2.5 mm²) (option M32)
Signal and control cables are connected directly to the terminals on Terminal Module TM31 or
TM15 as standard. The maximum connectable cross-section for these cables to the TM31 and
TM15 Terminal Modules is limited to 1.5 mm
2
.
With option M32, you can connect signal and control cables with connection cross-sections of
up to 2.5 mm
2
to a terminal strip via cage clamp terminals.
3.6.22
Controlled outgoing circuit for auxiliary equipment 400 V 3 AC (option N30)
This option includes a controlled outgoing feeder for external auxiliaries (3 AC 400 V, max.
4 KW). The controlled outgoing feeder is protected by a circuit breaker. The circuit breaker
setting range is cos phi = 0.8 (7 A up to 10 A).
The option can be used to operate external fans on motors and pumps and oil supply units. The
"ON" command at the drive closes the contactor. The "OFF" command opens the contactor.
Externally provide the necessary drive power supply. The terminal assignment is provided in
the circuit diagram of the drive.
Description
3.6 Description of options
SINAMICS SM150 6SL3810-7NN38-0AA1
Operating Instructions Rev.201910281406 EXAMPLE
67
Содержание SINAMICS SM150 6SL3810-7NN38-0AA1
Страница 2: ...28 10 2019 14 06 V32 00 ...
Страница 12: ...Table of contents SINAMICS SM150 6SL3810 7NN38 0AA1 12 Operating Instructions Rev 201910281406 EXAMPLE ...
Страница 106: ...Start up SINAMICS SM150 6SL3810 7NN38 0AA1 106 Operating Instructions Rev 201910281406 EXAMPLE ...
Страница 168: ...Spare parts SINAMICS SM150 6SL3810 7NN38 0AA1 168 Operating Instructions Rev 201910281406 EXAMPLE ...
Страница 172: ...Service Support SINAMICS SM150 6SL3810 7NN38 0AA1 172 Operating Instructions Rev 201910281406 EXAMPLE ...
Страница 183: ......
Страница 186: ......
Страница 188: ......