3.3.2
Design of the Active Line Module and Motor Module
The Active Line Module / Motor Module has three phases. For the number of IGBTs connected
in series N=2, each phase comprises five PowerCards. A PowerCard is equipped with two
neutral point diodes. Each of the other PowerCards has two power semiconductors that can be
switched off (IGBT modules) with integrated freewheeling diodes.
The IGBTs can limit and interrupt a short-circuit current. This means a short-circuit normally
generally results in a stop. This prevents device damage.
Figure 3-2
Active Line Module / Motor Module
3.4
Operating principle
A constant DC-link voltage for the Motor Module is generated from the line voltage. The Motor
Module provides the power for the connected motor via the DC-link voltage.
The DC link capacitors smooth the voltage and stop the energy in the DC link. The DC link
capacitors are maintenance free and self-healing. The device is switched off when the circuit
breaker is disconnected/opened. The DC link is discharged by means of balancing resistors.
3.5
Description of the components
Further information is available in the following documents:
● Additional information about connecting the various components is provided in the circuit
manual.
Description
3.5 Description of the components
SINAMICS SM150 6SL3810-7NN38-0AA1
Operating Instructions Rev.201910281406 EXAMPLE
31
Содержание SINAMICS SM150 6SL3810-7NN38-0AA1
Страница 2: ...28 10 2019 14 06 V32 00 ...
Страница 12: ...Table of contents SINAMICS SM150 6SL3810 7NN38 0AA1 12 Operating Instructions Rev 201910281406 EXAMPLE ...
Страница 106: ...Start up SINAMICS SM150 6SL3810 7NN38 0AA1 106 Operating Instructions Rev 201910281406 EXAMPLE ...
Страница 168: ...Spare parts SINAMICS SM150 6SL3810 7NN38 0AA1 168 Operating Instructions Rev 201910281406 EXAMPLE ...
Страница 172: ...Service Support SINAMICS SM150 6SL3810 7NN38 0AA1 172 Operating Instructions Rev 201910281406 EXAMPLE ...
Страница 183: ......
Страница 186: ......
Страница 188: ......