If the mushroom pushbutton is not installed in the drive cabinet, both control circuits of the "Safe
Torque Off" function are wired to the customer terminal strip. In complex systems the interface
via the terminal strip is used to integrate the "Safe Torque Off" function in the higher-level fail-
safe controller. According to the specification of the safety relays, the permissible cable length
at the safe inputs is 2000 m (1000 m 1000 m outward).
The "Safe Torque Off" mushroom pushbutton is a positively-opening mushroom pushbutton.
The mushroom pushbutton has the following features:
● Two NC contacts (dual-channel activation)
● Positive latching
● Rotate to release using the following elements:
– Actuating element
EMERGENCY STOP / EMERGENCY OFF control device according to ISO 13850/
EN 418 and IEC 60947-5-5, e.g. Siemens 3SB3000-1HA20.
– 2NC switching element
Positive opening according to IEC 60947-5-1, Annex K, e.g. Siemens 3SB3403-OE
The mushroom pushbutton is connected via a 4-wire shielded control cable with a wire cross
section ≥ 0.5 mm
2
, e.g. Gore GSC-01-4097-00 4 x AWG 20 (0.62 mm
2
). Choice of cables and
wiring system according to EN60204-1.
If the "Safe Torque Off" mushroom pushbutton is connected through a fail-safe PLC, this must
also be implemented with two channels. The PFH
D
value for all external devices connected to
terminal strip -X110 ("Safe Torque Off" mushroom pushbutton or "Safe Torque Off" mushroom
pushbutton and fail-safe controller) must be ≤ 0.5 x 10
-6
in total.
1
2
3
4
3
T
K
2
8
4
2
.
6DIH7RUTXH2II
;
<
< < <
1
2
3
4
.
6DIH7RUTXH2II
;
<
< < <
K
3
T
2
8
4
2
0XVKURRPSXVKEXWWRQ
H[WHUQDO
0XVKURRPSXVKEXWWRQ
IDLOVDIH
3/&
RU
6DIHW\UHOD\
6DIHW\UHOD\
H[WHUQDO
Figure 3-10
Connection possibilities - mushroom pushbutton "Safe Torque Off"
After closing the two control circuits of the 3TK2842 (releasing the mushroom pushbutton or
appropriate control signals on the terminal strip), to restart the drive requires an additional
second action of acknowledging the Safe Torque Off signal in the Control Unit. The drive can
be enabled by acknowledgment via an acknowledge button, which can be read-in via binary
input as well as via a higher-level automation (control platform). The acknowledge button must
Description
3.6 Description of options
SINAMICS SM150 6SL3810-7NN38-0AA1
Operating Instructions Rev.201910281406 EXAMPLE
51
Содержание SINAMICS SM150 6SL3810-7NN38-0AA1
Страница 2: ...28 10 2019 14 06 V32 00 ...
Страница 12: ...Table of contents SINAMICS SM150 6SL3810 7NN38 0AA1 12 Operating Instructions Rev 201910281406 EXAMPLE ...
Страница 106: ...Start up SINAMICS SM150 6SL3810 7NN38 0AA1 106 Operating Instructions Rev 201910281406 EXAMPLE ...
Страница 168: ...Spare parts SINAMICS SM150 6SL3810 7NN38 0AA1 168 Operating Instructions Rev 201910281406 EXAMPLE ...
Страница 172: ...Service Support SINAMICS SM150 6SL3810 7NN38 0AA1 172 Operating Instructions Rev 201910281406 EXAMPLE ...
Страница 183: ......
Страница 186: ......
Страница 188: ......