9.4.3.4
Checking the cable and screw terminals
● Check the cable and screw terminals regularly to ensure that they are secure.
● Tighten the screws if necessary. When doing this, comply with the specified torques
● Check the cabling for defects.
● Replace any defective parts immediately.
9.5
Maintenance
9.5.1
Replacing a fan
9.5.1.1
Lubricating fan bearings
Lubricate the fan bearings every six months, or more frequently as required.
1. Stop the motor. Open the switch.
2. Thoroughly clean the pipe connections and remove them from the housings.
3. Remove hardened grease from the grease discharge points using a stiff wire or a rod.
4. Press fresh grease into the bearing intake point using a manually operated press until a
small amount of fresh grease is pressed out of the discharge point.
5. Remove excessive grease from the connections, replace the intake plugs and allow the
motor to run for 1/2 hour before reinserting the grease discharge plugs.
6. Recommission the motor.
CAUTION
Injury caused by rotating fan
If the drive is equipped with a temperature and pressure-controlled fan, the fan can run on
even if the power unit is switched off. You can be injured if you touch the fan.
● Wait until the fan has shut down and has come to a stop.
9.5.1.2
Replacing fans, from the front
● The five safety rules must be observed.
● Be very careful when lifting the fans. The fans are heavy. The fans can fall if incorrectly
handled. This can cause injury and material damage.
Maintenance
9.5 Maintenance
SINAMICS PERFECT HARMONY GH150 6SL3826
Operating Instructions 05/2020
99
Содержание SINAMICS PERFECT HARMONY GH150 6SL3826
Страница 2: ...19 06 2020 09 25 V14 00 ...
Страница 120: ...Spare parts SINAMICS PERFECT HARMONY GH150 6SL3826 120 Operating Instructions 05 2020 ...
Страница 124: ...Service Support SINAMICS PERFECT HARMONY GH150 6SL3826 124 Operating Instructions 05 2020 ...
Страница 130: ...Quality documents SINAMICS PERFECT HARMONY GH150 6SL3826 130 Operating Instructions 05 2020 ...
Страница 132: ...Additional documents SINAMICS PERFECT HARMONY GH150 6SL3826 132 Operating Instructions 05 2020 ...
Страница 135: ......
Страница 136: ...Further Information www siemens com LDA Siemens AG Large Drives Applications Vogelweiherstr 1 15 90441 NÜRNBERG GERMANY ...