Commissioning
4.3 Frequently required parameters
CU250S-2 Control Units
22
Compact Operating Instructions, 05/2014, A5E32899990B AB
Description files for fieldbuses
The description files are electronic device data sheets which contain all the required
information of a higher-level controller. You can configure and operate the inverter on a
fieldbus with the appropriate description file.
Description file
Download
Alternative to download
Generic Station
Description (GSD) for
PROFIBUS
Internet:
GSD and GSDML are saved in the inverter. The
inverter writes its GSD or GSDML to the memory
card once you insert this card in the inverter and
set p0804 to 12. You can then transfer the file to
your programming device or PC using the
memory card.
GSD Markup Language
(GSDML) for
PROFINET
Internet:
Electronic Data Sheet
(EDS) for CANopen
Internet:
---
EDS for Ethernet/IP
---
Further information can be found in the operating
instructions
4.3
Frequently required parameters
Parameter
Explanation
p0015
Macro drive unit
Set defaults for inputs and outputs via a macro Terminal blocks (Page 10).
r0018
Control Unit firmware version
p0100
IEC/NEMA mot stds
0: Europe 50 [Hz]
1: NEMA motor (60 Hz, US units)
2: NEMA motor (60 Hz, SI units)
p0304
Rated motor voltage [V]
p0305
Rated motor current [A]
p0307
Rated motor power [kW] or [hp]
p0310
Rated motor frequency [Hz]
p0311
Rated motor speed [rpm]
p0601
Motor temperature sensor type
Terminal 14 T1 motor (+) 0: No sensor (factory setting)
1: PTC (→ p0604)
2: KTY84 (→ P0604)
4: Bimetal
Terminal 15 T2 motor (-)
p0625
Motor ambient temperature during commissioning [° C]
p0640
Current limit [A]