SIMOVERT MV Commissioning Instructions
%LW
,QFKLQJ
After the inching command has been accepted, the inching frequency is enabled in
the setpoint channel. When the signal is withdrawn, the setpoint, which is
parameterized as main- or supplementary setpoint, is enabled.
Inching is only enabled after the inverter-, ramp-function generator- and setpoint
have been enabled.
%LW
)UHH
%LW
&RQWUROIURPWKHDXWRPDWLRQV\VWHP
After the command has been accepted, the process data PZD (control word,
setpoints) are evaluated, which are sent via the interface. Otherwise, the last
interface values which were saved, are maintained.
%LW
&ORFNZLVHURWDWLQJILHOGVHOHFWLRQ
After the command for clockwise rotating field
has been accepted, depending on
the assignment of the "counter-clockwise rotating field" command, the setpoint is
influenced. The counter-clockwise/clockwise changeover is enabled in parameter
P330. A defined changeover must be made at the selected sources. If none, or
both directions are selected, then the alarm message "undefined direction of
rotation" alarm message is output
%LW
&RXQWHUFORFNZLVHURWDWLQJILHOGVHOHFWLRQ
After the command for counter-clockwise rotating field
has been accepted, the
setpoint is influenced depending on the assignment of the "clockwise rotating field"
command. Refer to the "Function diagram, setpoint channel". The counter-
clockwise/clockwise changeover is enabled in parameter P330. The selected
sources must be changed-over in a defined fashion. If none, or both directions of
rotation are selected, the "direction of rotation undefined" alarm message is output
%LW
0RWRUL]HGSRWHQWLRPHWHUUDLVH
After the command has been accepted, the motorized potentiometer is controlled
in the setpoint channel according to the assignment of the "motorized
potentiometer, lower" command. Also refer to "function diagram, setpoint channel".
%LW
0RWRUL]HGSRWHQWLRPHWHUORZHU
After the command has been accepted, the motorized potentiometer is controlled
in the setpoint channel, depending on the assignment of the "motorized
potentiometer, raise". command. Also refer to the "function diagram, setpoint
channel".
%LW
([WHUQDOIDXOW
After the command has been accepted, the system changes-over into the FAULT
status.
The inverter pulses are inhibited and the circuit-breaker is opened.