SIMOVERT MV Commissioning Instructions
5.2.7
Status displays
A binary vector can be switched to the actual value display V24 [SHIFT + V12]
using key V23 [SHIFT + V11]. This allows internal drive converter statuses to be
visualized using the operator panel.
The following signals can be selected using key V23. The actual values of the
selected signals can be visualized in V24.
Guideline:
All signals are high-active (log 1 the command/status is present).
Exceptions are specifically referred to.
The drive converter executes the commands available at the power-on logic in
control words 1 and 2. These control words are listed in function package I/O (refer
to Fig. 4.1) The command sources for the individual control word bits are also
defined in function package I/O.
&RQWUROZRUGDWWKHSRZHURQORJLF
V23 input value = 1
V24 actual value =
FRQWUROZRUG
at the power-on logic
%LW
ON / OFF 1 (a log. 1 the ON command)
%LW
OFF2 (a log.1 the OFF2 command)
%LW
OFF3 (a log. 1 the OFF3 command)
%LW
Inverter enable (a log. 1 inverter enable)
%LW
Ramp-function generator enable (a log. 1 RFG enable)
%LW
Ramp-function generator hold (a log. 1 RFG hold)
%LW
Setpoint enable (a log. 1 setpoint enable)
%LW
Acknowledge (a log. 1 acknowledge command; 1 s pulse)
%LW
Inching (a log. 1 inching command)
%LW
Free
%LW
Control from the automation system (a log. 1 control from the automation
system)
%LW
Clockwise rotating field selection (a log. 1 CRF)
%LW
Counter-clockwise rotating field selection (a log. 1 CCRF)
%LW
Motorized potentiometer, raise (a log. 1 command, raise motorized
potentiometer)
%LW
Motorized potentiometer, lower (a log. 1 command, lower motorized
potentiometer)
%LW
External fault (a log. 1 fault)