SIMOVERT MV Commissioning Instructions
5.2.4
Setpoint inputs
3URFHVVGDWDSURFHVVLQJ
9$/
'LVSOD\LQJSURFHVVLQJGDWD
The last two pieces of process data are displayed (presetting: Values V1
and V2).
SEL
6HOHFWLQJSURFHVVGDWD
The select functions V1 ... V12 / SHIFT / DIM) are activated.
The designator flashes in the active display line.
The active display line changes when the key is pressed again.
V1
...
V12
SHIFT
DIM
Selects process data
Toggles between the
Toggles between
V1 ... V12: Meas. value 1 ... 24
process data panels
value display with dimension-
LED dark:
V1 ... V12
and value displayed as
LED bright
V13 ... V24
percentage
CHG
&KDQJLQJVHWSRLQWV
The change mode is switched-in for the selected process data.
A change which is being made is aborted.
Operating message No. 5 ”SETPOINT CHANGE INHIBITED”, if an actual
value was selected (configuring).
Numerica
l keypad
Re-input value
less
greater
Changing the value with the-
continuous change keys and inching
Backspace key
Changeover between
mantissa and exponent
for floating numbers
Cursor position
Cursor- position
New value input
Enter
Completes and transfers
the change
EPROM
6DYLQJFKDQJHVLQWKH(3520RI6,0$'<1'
Activating the memory function
The LED flashes until the function is completed using the Enter key.
Operating message No. 35 ”EPROM SAVE UNSUCCESSFUL”. The value is
not transferred if an error occurred.
Enter
9DOXHWUDQVIHU
The currently executed function is aborted using:
6<67(0
6<6
06*
9$/
%,1
Return to display operation:
06*