Supplementary system components
6.3 TB30 terminal board
SIMOTION D4x5-2
104
Manual, 02/2012
6.3.3.5
Analog inputs and outputs
Table 6- 8
Terminal block X482
Terminal
Designation
1)
1
AI 0+
2
AI 0-
3
AI 1+
4
AI 1-
5
AO 0+
6
AO 0-
7
AO 1+
8
AO 1-
Table 6- 9
X482 wiring
Characteristics
Type
Connectable conductor types
- Rigid
- Flexible
- Flexible with end sleeve, without plastic sleeve
- AWG/kcmil
Conductor cross-section
0.14 mm
2
to 0.5 mm
2
0.14 mm
2
to 0.5 mm
2
0.25 mm
2
to 0.5 mm
2
26 to 20
Stripped length
8 to 9 mm
Tool
Screwdriver 0.4 x 2.0 mm
Max. cable length
30 m
Note
An open input is interpreted as approximately "0 V".
The power supply of the analog I/Os of the TB30 is via the option slot of the D4x5-2 control
unit and not via X424.
The shield is connected to the control unit. For further information concerning "Establishing a
shield connection", refer to the
SIMOTION D4x5-2 Commissioning and Hardware Installation
Manual, "Connecting I/Os" section.
CAUTION
The common-mode range must not be infringed.
The analog differential voltage signals can have a maximum offset voltage of ±30 V with
respect to the ground potential. If the range is infringed, incorrect results may occur during
analog/digital conversion.
Содержание SIMOTION TB30
Страница 10: ...Table of contents SIMOTION D4x5 2 10 Manual 02 2012 ...
Страница 36: ...Description 1 9 CompactFlash card SIMOTION D4x5 2 36 Manual 02 2012 ...
Страница 46: ...Operator control hardware 2 3 7 segment and LED displays SIMOTION D4x5 2 46 Manual 02 2012 ...
Страница 72: ...Interfaces 3 10 USB interfaces SIMOTION D4x5 2 72 Manual 02 2012 ...
Страница 134: ...Supplementary system components 6 11 DMC20 DRIVE CLiQ hub SIMOTION D4x5 2 134 Manual 02 2012 ...
Страница 142: ...Standards and approvals A 3 Safety of electronic controllers SIMOTION D4x5 2 142 Manual 02 2012 ...
Страница 150: ...Index SIMOTION D4x5 2 150 Manual 02 2012 ...