SIMO_CHN Function
3.2 Inputs / Outputs
SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.0 SP2
Programming and Operating Manual, 09/2019, A5E48307694002A/RS-AA/001
25
I/O Parameter
Meaning
Data Type
Default setting Type OCM Permissible
Values
Q1_4
SIMOCODE DP 1.4: not used
BOOL
FALSE
O
Q1_5
SIMOCODE DP 1.5: not used
BOOL
FALSE
O
Q1_6
SIMOCODE DP 1.6: not used
BOOL
FALSE
O
Q1_7
SIMOCODE DP 1.7: not used
BOOL
FALSE
O
QADD_F1
1=additional function 1 active
BOOL
FALSE
O
+
QADD_F2
1=additional function 2 active
BOOL
FALSE
O
+
QADDF1OP
1=operator enabled for input ADD F1
BOOL
FALSE
O
+
QADDF2OP
1=operator enabled for input ADD F2
BOOL
FALSE
O
+
QAUTOP
1=operator enabled for input AUTO
BOOL
FALSE
O
+
QBAD
1=invalid process value
BOOL
FALSE
O
QCSF
Control System Fault: 1=External Error
BOOL
FALSE
O
+
QCST
SIMOCODE DP 1.0: Test (CST)
BOOL
FALSE
O
+
QCTA
SIMOCODE DP 1.1: cooling time active BOOL
FALSE
O
+
QCUR
motor current is flowing
BOOL
FALSE
O
+
QCUR_AH
1=current high limit alarm reached
BOOL
FALSE
O
QCUR_AL
1=current low limit alarm reached
BOOL
FALSE
O
QCUR_WH
1=current high LIMIT warning reached
BOOL
FALSE
O
QCUR_WL
1=current low limit warning reached
BOOL
FALSE
O
QEM_START
SIMOCODE DP 0.4: 1=emergency start
active
BOOL
FALSE
O
QENSDCS
1=enable internal updating of record
130/131/133
BOOL
TRUE
O
+
QERR
1=Program error
BOOL
FALSE
O
+
QERR_RCS
1=error reading control/signal data
(record 130)
BOOL
FALSE
O
QERR_RSD
1=error reading statistic data (record 131) BOOL
FALSE
O
QERR_WSD
1=error writing statistic data (record 133) BOOL
FALSE
O
QG_FLT
SIMOCODE DP 0.6: general fault
BOOL
FALSE
O
+
QG_WRN
SIMOCODE DP 0.7 AND NOT DP 0.3:
general warning
BOOL
FALSE
O
+
QLOCOP
1=operator enabled for input
LOCAL/REMOTE
BOOL
FALSE
O
+
QLTA
SIMOCODE DP 0.4: lock time active
BOOL
FALSE
O
+
QMAN_AUT
1=AUTO; 0=MANUAL
BOOL
FALSE
O
+
QMAN_MOP
1=MANUAL-LINKED;
0=MANUALOPERATOR
BOOL
FALSE
O
+
QMANLOP
1=operator enabled for input MANUAL
LINKED/MANUAL OP
BOOL
FALSE
O
+