SIMO_CHN Function
3.2 Inputs / Outputs
SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.0 SP2
22
Programming and Operating Manual, 09/2019, A5E48307694002A/RS-AA/001
3.2
Inputs / Outputs
I/O Parameter
Meaning
Data Type
Default setting Type OCM Permissible
Values
ADD_F1
operator input: 1=additional function 1
active
BOOL
FALSE
I
+
ADD_F2
operator input: 1=additional function 2
active
BOOL
FALSE
I
+
ADDF1_EN
ENABLE: 1=operator may input ADD_F1 BOOL
TRUE
I
ADDF2_EN
ENABLE: 1=operator may input ADD_F2 BOOL
TRUE
I
AUT_L
Linkable Input for Manual/Auto Mode
BOOL
FALSE
I
AUTO_M
1=AUTO_ON1, AUTO_OFF, AUTO_ON2
active 0=AUTO_ON, AUTO_OPT active
BOOL
FALSE
I
AUTO_OFF
AUTO: AUTO_M=1: 1=switch off/stop
BOOL
FALSE
I
AUTO_ON
AUTO: AUTO_M=0: 1=on; 0=off/stop
BOOL
FALSE
I
AUTO_ON1
AUTO: AUTO_M=1: 0->1=switch on
slow/reverse/close
BOOL
FALSE
I
AUTO_ON2
AUTO: AUTO_M=1: 0->1=switch on
fast/forward/open
BOOL
FALSE
I
AUTO_OPT
AUTO: AUTO_M=0:
1=slow/reverse/close;
0=fast/forward/open
BOOL
FALSE
I
AUTON_OP
operator input mode: 1=AUTO;
0=MANUAL
BOOL
FALSE
I
+
AUTOP_EN
ENABLE: 1=operator may input AUTO
BOOL
TRUE
I
BA_EN
Batch enable
BOOL
FALSE
I
+
BA_ID
Batch ID
DWORD
16#0
I
+
BA_NA
BATCH name
STRING[32] ‘’
I
+
COOL_T
cooling time in [s]
WORD
16#0
O
+
COUNT1
counter 1
WORD
16#0
O
COUNT2
counter 2
WORD
16#0
O
CS_0
control/signal data (record 130) byte 0
BYTE
16#0
O
CS_1
control/signal data (record 130) byte 1
BYTE
16#0
O
CS_2
control/signal data (record 130) byte 2
BYTE
16#0
O
CS_3
control/signal data (record 130) byte 3
BYTE
16#0
O
CS_4
control/signal data (record 130) byte 4
BYTE
16#0
O
CS_5
control/signal data (record 130) byte 5
BYTE
16#0
O
CS_6
control/signal data (record 130) byte 6
BYTE
16#0
O
CS_7
control/signal data (record 130) byte 7
BYTE
16#0
O
CS_8
control/signal data (record 130) byte 8
BYTE
16#0
O
CS_9
control/signal data (record 130) byte 9
BYTE
16#0
O
CS_UPD
0->1: update Diagnostic Data
BOOL
FALSE
IO
+
CUR
motor current in %Ie
REAL
0
O
+
CUR_AH
HH Alarm LIMIT in %Is
REAL
130.0
I
+