Migration (Legacy) - V9.0 SP2 

Programming and Operating Manual 

 

 

09/2019 

A5E48307694002A/RS-AA/001 

Introduction 

 

 

SIMODIAG Function  

 

 

SIMO_CHN Function  

 

 

 

 

 

 

 

 

Содержание SIMOCODE DP

Страница 1: ...gration Legacy V9 0 SP2 Industrial Controls SIMOCODE DP SIMOCODE DP PCS 7 Library Migration Legacy V9 0 SP2 Programming and Operating Manual 09 2019 A5E48307694002A RS AA 001 Introduction 1 SIMODIAG Function 2 SIMO_CHN Function 3 ...

Страница 2: ...may be operated only by personnel qualified for the specific task in accordance with the relevant documentation in particular its warning notices and safety instructions Qualified personnel are those who based on their training and experience are capable of identifying risks and avoiding potential hazards when working with these products systems Proper use of Siemens products Note the following WA...

Страница 3: ...oring 8 2 2 Inputs Outputs 9 2 3 Message Texts and Auxiliary Process Values 10 2 4 Description of Parameters 10 2 4 1 OMODE structure 10 3 SIMO_CHN Function 11 3 1 Description 11 3 1 1 Object Name Type Number 11 3 1 2 Calling OBs 11 3 1 3 Function 11 3 1 4 Project configuration 12 3 1 5 Principle of Operation 14 3 1 6 Module Failure 14 3 1 7 Simulation 15 3 1 8 Local Remote switch over of the Cont...

Страница 4: ...3 2 Inputs Outputs 22 3 3 Message Texts and Auxiliary Process Values 29 3 3 1 Message Texts and Auxiliary Process Values 29 3 4 AS block parameters in the CFC 31 3 5 Description of Parameters 34 3 5 1 Control Functions 34 3 5 2 INBT2 assignment 36 3 5 3 OBT2 assignment 38 3 5 4 SIMO_STAT Status Display 39 3 5 5 VSTATUS and VSTATUS1 Status Display 40 3 6 Display in WinCC 41 3 6 1 Views 41 3 6 2 Sta...

Страница 5: ...tems machines and components should only be connected to an enterprise network or the internet if and to the extent such a connection is necessary and only when appropriate security measures e g firewalls and or network segmentation are in place For additional information on industrial security measures that may be implemented please visit https www siemens com industrialsecurity Siemens products ...

Страница 6: ...uct specific security information Product specific security information This library is designed to run under the PCS 7 environment Therefore it is recommended to follow the security principles for PCS 7 to support a secure operation such as User rights Password protection of WinCC SIRIUS devices For more information click here https support industry siemens com cs document 60119725 ...

Страница 7: ... DPV1 The block evaluates the related acyclic system events startup module error etc It generates messages and provides status information for the SIMO_CHN on the OMODE output SIMODIAG is not used in systems with Y Link DPV0 In this case the SIMO_CHN block is linked to driver block PADP_L00 2 1 4 Use in CFC When using the CFC Generate Module Driver function the following are performed automaticall...

Страница 8: ...operly output QMODF is set and the higher level error identifier OMODE 16 40xxxxxx is written to output OMODE The SIMOCODE DP Module Failure message is also generated 2 1 8 I O access error From the viewpoint of the I O configuration SIMOCODE DP is a compact DP Slave i e it always has a fixed I O configuration If there is an I O access error therefore a general DP Slave failure is assumed and indi...

Страница 9: ... Message failure WORD 16 0 O OMODE Status MODE DWORD 16 0 O QERR 1 Program error BOOL FALSE O QMODF 1 Module I O Access Failure BOOL FALSE O QPERAF Access error BOOL FALSE O QRACKF 1 Rack Error BOOL FALSE O RACK_NO Rack number BYTE 16 0 I RACK1ERR 1 DP Slave system failure BOOL FALSE O RACK2ERR 1 Redundant DP Slave system failure BOOL FALSE O RACKF 1 Rack Error BOOL FALSE I SLOT_NO Slot number BYT...

Страница 10: ...le Failure 1 d 2 d 3 d S EN_MSG The auxiliary process values are assigned as follows Auxiliary process value Block parameter Meaning 1 SUBN_ID DP master system ID 2 RACK_NO Rack Station number 3 SLOT_NO Slot number Refer Inputs Outputs Page 9 2 4 Description of Parameters 2 4 1 OMODE structure Byte 3 Byte 2 Byte 1 and 0 16 80 Valid data 16 01 Restart OB100 completed MODE input 16 40 Invalid data M...

Страница 11: ... OB in which the block is installed e g OB32 Also in OB 100 see Startup Response 3 1 3 Function The function block is used for operating and monitoring the SIMOCODE DP 3UF5 motor protection and control device The following 9 control functions are supported Sl no Control functions 1 Overload OVL 2 Direct starter DIR 3 Reversing starter REV 4 Star delta starter STAR 5 Dahlander starter DAHL 6 Pole c...

Страница 12: ...o enable the communication functionality of the SIMOCODE DP device on the PROFIBUS network Condition The PROFIBUS DP master is a CP 443 5 Extended MLFB 6GK7 443 5DX03 0XE0 The Operating Mode of the DP network is DPV1 SIMATIC PDM is installed SIMOCODE DP Basic parameterization There are SIMOCODE DP device parameters that must be set initially e g using the software WinSIMOCODE DP to enable the comm...

Страница 13: ...selection would also be S7 Compatible SIMOCODE DP behind the Y Link DPV1 Open STEP 7 HW Config From the Hardware Catalog Profile standard navigate to PROFIBUS Devices Switching Devices SIMOCODE DP PDM Place this device on the PROFIBUS network Note Here DP corresponds to the SIMOCODE DP device parameter Operating Mode DP norm In this configuration DPV1 data record functions are not available Assign...

Страница 14: ...d through the process image To do this parameter inputs INBT2_01 2 binary data bytes and INBT2_23 2 current bytes and parameter outputs OBT2_01 2 binary data bytes and OBT2_23 2 binary data bytes are linked to the associated inputs or outputs of the SIMOCODE DP device 3 1 5 Principle of Operation In program file Blocks Templates the SIMOCODE DP PCS 7 Library Migration Legacy V9 0 SP2 provides temp...

Страница 15: ...output as 0 when simulation is switched on Output QBAD is set depending on QCSF and QSIM QBAD QCSF AND NOT QSIM In normal operation SIM_ON FALSE the value corresponds to output QCSF and indicates an invalid process value A simulation value can thus be treated as a valid process value for testing purposes in the event of an error 3 1 8 Local Remote switch over of the Control Station The control sta...

Страница 16: ...d by safety position SS_POS VL_OPEN causes selection of OPEN position and VL_CLOSE causes selection of CLOSED position VL_HOLD is only active in the POS control function and causes the positioner to stop at its current position Block I O DIR SOFT STAR REV POL DAHL VALVE POS LOCK Motor switches OFF Motor switches OFF Solenoid valve runs in position defined by SS_POS OPEN or CLOSED Positioner runs i...

Страница 17: ... are active Manual In manual mode the control commands are set by the operator either at the OS or through linked inputs The linked inputs are L_ON1 L_OFF and L_ON2 Control from the OS is performed through inputs ON1_OP OFF_OP ON2_OP For control through the OS operator enabling signals QON1OP QOFFOP and QON2OP are required These signals are set depending on control function SIMO_FCT the active ope...

Страница 18: ...ndicated where appropriate The limit values are configured at the OS through inputs CUR_AH CUR_WH CUR_WL and CUR_AL A hysteresis value HYS can also be set The indications are provided through outputs QCUR_AH QCUR_WH QCUR_WL and QCUR_AL Output QCUR is used to indicate whether a current is flowing Motor monitoring is only active when the current goes above minimum value CUR_MIN default value of CUR_...

Страница 19: ... by linkable input parameter L_SD_UPD or by the OS when the associated faceplate views are opened or by an OS control SD_UPD The read data are output on parameters OPH operating hours N_START number of starts N_OVL number of overload trips COUNT1 COUNT2 counter statuses COOL_T cooling time TRIP_CUR trip current and SENSOR analog sensor value If reading was not possible the values are cleared and o...

Страница 20: ...hrough the two inputs ADDF1_EN and ADDF2_EN QADDF1OP and QADDF2OP These additional functions do not affect the internal block functions and can be used for controlling any of the binary signals 3 1 17 Startup Response After CPU startup restart the current statuses for LOCAL REMOTE MANUAL AUTO MANUAL OPERATOR MANUAL LINKED are retained Commands are not output again Depending on the configured SIMOC...

Страница 21: ...block uses the Alarm_8P block for generating messages Messages can be triggered by monitoring of motor current limit values SIMOCODE_DP signals linkable message input 3 1 22 Faceplate actuation Special signals are generated in the block to actuate the block icon and faceplate These signals are SIMO_OVL SIMO_STAT VSTATUS and VSTATUS1 SIMO_OVL is a binary output which is set if SIMOCODE is configure...

Страница 22: ...pen BOOL FALSE I AUTO_OPT AUTO AUTO_M 0 1 slow reverse close 0 fast forward open BOOL FALSE I AUTON_OP operator input mode 1 AUTO 0 MANUAL BOOL FALSE I AUTOP_EN ENABLE 1 operator may input AUTO BOOL TRUE I BA_EN Batch enable BOOL FALSE I BA_ID Batch ID DWORD 16 0 I BA_NA BATCH name STRING 32 I COOL_T cooling time in s WORD 16 0 O COUNT1 counter 1 WORD 16 0 O COUNT2 counter 2 WORD 16 0 O CS_0 contr...

Страница 23: ...eive Bit 1 4 BOOL FALSE I I1_5 SIMOCODE DP Receive Bit 1 5 BOOL FALSE I I1_6 SIMOCODE DP Receive Bit 1 6 BOOL FALSE I I1_7 SIMOCODE DP Receive Bit 1 7 BOOL FALSE I I23 SIMOCODE DP Receive Bit 2 0 3 7 WORD 16 0 I INBT2_01 process value DP 0 0 1 7 basic type 2 WORD 16 0 I INBT2_23 process value motor current basic type 2 WORD 16 0 I L_CS_UPD linkable input 0 1 update record 130 BOOL FALSE I L_OFF MA...

Страница 24: ...VID Message ID DWORD 16 0 I MSG_LOCK Enable 1 Messages locked BOOL FALSE I MSG_STAT Message STATUS Output WORD 16 0 O N_OVL number of overload trips WORD 16 0 O N_OVL_S set value number of overload trips WORD 16 0 IO N_STRT number of starts DWORD 16 0 O N_STRT_S set value number of starts DWORD 16 0 IO OBT2_01 process value DP 0 0 1 7 basic type 2 WORD 16 0 O OBT2_23 process value DP 2 0 3 7 basic...

Страница 25: ...ime active BOOL FALSE O QCUR motor current is flowing BOOL FALSE O QCUR_AH 1 current high limit alarm reached BOOL FALSE O QCUR_AL 1 current low limit alarm reached BOOL FALSE O QCUR_WH 1 current high LIMIT warning reached BOOL FALSE O QCUR_WL 1 current low limit warning reached BOOL FALSE O QEM_START SIMOCODE DP 0 4 1 emergency start active BOOL FALSE O QENSDCS 1 enable internal updating of recor...

Страница 26: ...FALSE O QOFFOP 1 operator enabled for input OFF BOOL FALSE O QON1 SIMOCODE DP 0 0 status ON1 BOOL FALSE O QON1OP 1 operator enabled for input ON1 BOOL FALSE O QON2 SIMOCODE DP 0 2 status ON2 BOOL FALSE O QON2OP 1 operator enabled for input ON2 BOOL FALSE O QOVL SIMOCODE DP 0 3 status overload warning BOOL FALSE O QREMOTE SIMOCODE DP 0 5 1 REMOTE 0 LOCAL SIMOCODE BOOL FALSE O QSIM 1 Simulation acti...

Страница 27: ...E DP 0 1 status OFF 16 0004 SIMOCODE DP 0 2 status ON2 16 0008 SIMOCODE DP 0 3 status overload 16 0010 SIMOCODE DP 0 4 lock time active 16 0020 SIMOCODE DP 0 5 remote 16 0040 SIMOCODE DP 0 6 general fault 16 0080 SIMOCODE DP 0 7 general warning 16 0100 SIMOCODE DP 1 0 status CST 16 0200 SIMOCODE DP 1 1 status idle time active 16 0400 SIMOCODE DP 1 2 status positioner run open 16 0800 SIMOCODE DP 1...

Страница 28: ...ESET Operator Input 1 Reset SIMOCODE faults BOOL FALSE IO SS_POS Safe Position 1 Open 0 Close BOOL FALSE I STEP_NO Batch Step Number DWORD 16 0 I TIME_CLASS time in s to suppress current alarms after current flows REAL 10 I TIME_MON Monitoring Time for ON1 OFF ON2 s 0 REAL 5 I 0 TRIP_CUR tripping current in Is WORD 16 0 O VL_CLOSE 1 Lock to CLOSE BOOL FALSE I VL_HOLD 1 Lock to current position FAL...

Страница 29: ...umber Block Parameter Text Message Class Can be inhibited by 1 QCUR_AH BlockComment Current HH Alarm AH MSG_LOCK M_SUP_C 2 QCUR_WH BlockComment Current H Warning WH MSG_LOCK M_SUP_C 3 QCUR_WL BlockComment Current L Warning WL MSG_LOCK M_SUP_C 4 QCUR_AL BlockComment Current LL Alarm AL MSG_LOCK M_SUP_C 5 QG_WRN BlockComment General Warning 4 d 5 d S MSG_LOCK M_SUP_SMC 6 QG_FLT BlockComment General ...

Страница 30: ... general warning or general fault in SIMOCODE DP the current diagnostic information is transferred in the form of auxiliary process values provided that the required enable signals are present By updating this information the output of messages QG_FLT and QG_WRN can be delayed by up to 10 processing cycles maximum The Check back Signal Test CST is derived directly from the SIMOCODE DP information ...

Страница 31: ...HH alarm CUR_WH H alarm CUR_WL L alarm CUR_AL LL alarm EM_START Emerg Start OFF Emerg Start ON HYS Hysteresis M_SUP_C Enable Cur Alarm Suppr Cur Alarm M_SUP_EXT Enable Ext Alarm Suppr Ext Alarm M_SUP_SIMO Enabl SIMO Alarm Suppr SIMO Alarm MANON_OP Station OPERATOR Station LINKED MO_PVHR Bar UL MO_PVLR Bar LL MONITOR Monitoring OFF Monitoring ON MSG_LOCK Enable Alarms Suppr Alarms N_OVL No OVL Trip...

Страница 32: ...S block parameters contained in the CFC Template OVL to the I O fields of the faceplate Parameter S7_string_0 S7_string_1 ON1_OP 0 Command not act OFF_OP 0 Command not act ON2_OP 0 Command not act QON1 0 not act QOFF 0 not act QON2 0 not act LOCK_OPT not act not act SS_POS not act not act Assignment of AS block parameters contained in CFC Template DIR SOFT STAR to the I O fields of the faceplate P...

Страница 33: ...late Parameter S7_string_0 S7_string_1 ON1_OP 0 Command REVERSE OFF_OP 0 Command OFF ON2_OP 0 Command FORWARD QON1 0 REVERSE QOFF 0 OFF QON2 0 FORWARD LOCK_OPT ON REVERSE SS_POS not act not act Assignment of AS block parameters contained in the CFC Template POL DAHL to the I O fields of the faceplate Parameter S7_string_0 S7_string_1 ON1_OP 0 Command SLOW OFF_OP 0 Command OFF ON2_OP 0 Command FAST...

Страница 34: ...ive not active not active 1 Off 1 Off 1 Off L_ON2 not active not active not active 1 On 1 Forw 1 Fast ON1_OP not active not active not active not active 1 Rev 1 Slow OFF_OP not active not active not active 1 Off 1 Off 1 Off ON2_OP not active not active not active 1 On 1 Forw 1 Fast Active commands depending on control functions DAHL VALVE POS AUTO_M 0 AUTO_M 1 DAHL VALVE POS AUTO_ON X 0 Off 0 Off ...

Страница 35: ...N and LOCK_OPT or VL_OPEN VL_CLOSE VL_HOLD 5 AUTO with AUTO_M 6 AUTO 7 MANUAL LINKED 8 MANUAL OPERATOR The commands are set in positions 3 8 A command is reset when the associated check back signal is present or an associated equivalent signal or a higher level error or general fault occur in SIMOCODE DP Note For control functions REV POL and POS the appropriate opposite direction or speed is swit...

Страница 36: ...DP Byte 0 DP Bit 0 0 Send 144 Status On1 0 1 Status Off QOFF Profibus DP Byte 0 DP Bit 0 1 Send 145 Status Off 0 2 Status On2 QON2 Profibus DP Byte 0 DP Bit 0 2 Send 145 Status On2 0 3 Overload warning QOVL Profibus DP Byte 0 DP Bit 0 3 Send 147 Status overload warning 0 4 Interlock time active QLTA Profibus DP Byte 0 DP Bit 0 4 Send 148 Status lock time active 0 5 Local Remote QREMOTE Profibus DP...

Страница 37: ...er level errors e g a device failure through the MODE input Quality code CUR_QC is taken from the high byte of the MODE input If the byte 16 80 the read values in the process image are valid otherwise the values are treated as invalid and output QCSF is set CUR_QC can have the following values State CUR_QC Valid value 16 80 or 16 20 Simulation 16 60 Invalid value Otherwise e g 16 00 The settings i...

Страница 38: ...DM WinSIMOCODE DP 0 0 On1 command SPS PLS DP On1 056 DP Bit 0 0 Receive 0 1 Off command SPS PLS DP Off 057 DP Bit 0 1 Receive 0 2 On2 command SPS PLS DP On2 058 DP Bit 0 2 Receive 0 3 Not used Standard function blocks Test1 059 DP Bit 0 3 Receive 0 4 Emergency start EM_START Standard function blocks Emergency start 060 DP Bit 0 4 Receive 0 5 Local Remote REM_L REMON_OP Operating mode switch S1 061...

Страница 39: ...9 2019 A5E48307694002A RS AA 001 39 3 5 4 SIMO_STAT Status Display SIMO_STAT is used to actuate the status display Low Byte identifier for the respective device state see Actuation of Status Display High Byte identifier for SIMOCODE Function 16 00 OVL 16 08 SOFT 16 10 DIR 16 20 REV 16 30 STAR 16 40 DAHL 16 50 POL 16 60 VALVE 16 70 POS ...

Страница 40: ...N_AUT VSTATUS Bit_04 QADD_F2 VSTATUS Bit_19 QREMOTE VSTATUS Bit_03 Q1_6 VSTATUS Bit_18 QCST VSTATUS Bit_02 Q1_7 VSTATUS Bit_17 QSIM VSTATUS Bit_01 QMON_ERR VSTATUS Bit_16 LOCKED VSTATUS Bit_00 QMAN_MOP VSTATUS1 Bit_31 QAUTOP VSTATUS1 Bit_15 not used VSTATUS1 Bit_30 QMANOP VSTATUS1 Bit_14 not used VSTATUS1 Bit_29 QMANLOP VSTATUS1 Bit_13 not used VSTATUS1 Bit_28 QLOCOP VSTATUS1 Bit_12 not used VSTAT...

Страница 41: ...l in picture SIMO_CHN_SYMBOL PDL must be copied to the picture PCS7Typicals PDL so that the SIMOCODE symbol can be automatically inserted in the corresponding pictures when executing the Plant Hierarchy Create Update Picture Symbols function If you want to insert the SIMOCODE symbol into a process picture manually copy the lower SIMOCODE symbol into picture Templates PDL and use it for this config...

Страница 42: ...DE DP PCS 7 Library Migration Legacy V9 0 SP2 42 Programming and Operating Manual 09 2019 A5E48307694002A RS AA 001 Overview window Tagname Tooltip comment Event state Collect value MSG_LOCK QMSG_SUP Occupied Selection view Selection group display ...

Страница 43: ...rating Manual 09 2019 A5E48307694002A RS AA 001 43 Standard view Operation mode QMAN_AUT AUTON_OP QMANOP QAUTOP Station QMAN_MOP MANON_OP QMANLOP Active command ON1_OP ON2_OP OFF_OP QON1OP QON2OP QOFFOP LOCK LOCK_ON Lock option LOCK_OPT LOCK_OPT string Reset of SIMOCODE faults SIMORESET Reset of QMON_ERR RESET ...

Страница 44: ... SIMOCODE DP Overload OVL control function the display of operating mode station command and monitoring is disabled In SIMOCODE DP control function Direct starter DIR Star Delta STAR Soft starter SOFT and Solenoid valve VALVE the operation of the ON1 command is disabled In the symbol picture and the standard view a device failure is indicated by a change of color in the status display All inputs r...

Страница 45: ...L alarm CUR_AL Bar upper limit MO_PVHR Bar lower limit MO_PVLR In the SIMOCODE Solenoid Valve VALVE function limit value inputs and message suppression are disabled All inputs require operator level6 Operator enabling at login is linked through the direct connection of picture element Level6 Operator Enabling Permissions Operator Enabling The operator enabling and background colors for the other I...

Страница 46: ...e TIME_MON Emergency start EM_START QEMSTART In the SIMOCODE Overload OVL function the display of Local Remote Mon Time and Monitoring ON is disabled In the Solenoid Valve VALVE function Emerg Start is disabled Inputs Local Remote Add Function1 and Add Function2 require operator level5 all other inputs require operator level6 Operator enabling at login is linked through the direct connection of pi...

Страница 47: ...SOR unit Cooling time COOL_T COOL_T unit Trip current TRIP_CUR TRIP_CUR unit Update CS_UPD QENSDCS When a picture is selected SD_UPD is set Input Update requires operator level5 all other inputs require operator level6 Operator enabling at login is linked through the direct connection of picture element Level5 Operator Enabling Permissions Operator Enabling The operator enabling and background col...

Страница 48: ... 0 SP2 48 Programming and Operating Manual 09 2019 A5E48307694002A RS AA 001 Trend view Picture CONL1_Standard PDL is output Motor current CUR is displayed as an online variable No archiving is necessary The settings can be changed on the picture symbol through the ReturnPath property ...

Страница 49: ...SIMO_CHN Function 3 6 Display in WinCC SIMOCODE DP PCS 7 Library Migration Legacy V9 0 SP2 Programming and Operating Manual 09 2019 A5E48307694002A RS AA 001 49 Alarms view ...

Страница 50: ...ound Active property is enabled in displays CS_60 67 CS_70 77 or CS_80 87 by means of C scripts This indicates which bits are set in the status byte The colors of the individual indicators can be defined through the Background Flashing Color On and Background Flashing Color Off property Input Update requires operator level5 operator enabling at login is linked through the direct connection of pict...

Страница 51: ... Active property is enabled in displays CS_40 47 or CS_50 57 by C scripts This indicates which bits are set in the status byte The colors of the individual indicators can be defined through the Background Flashing Color On and Background Flashing Color Off property Input Update requires operator level5 operator enabling at login is linked through the direct connection of picture element Level5 Ope...

Страница 52: ...SIMO_CHN Function 3 6 Display in WinCC SIMOCODE DP PCS 7 Library Migration Legacy V9 0 SP2 52 Programming and Operating Manual 09 2019 A5E48307694002A RS AA 001 Batch view ...

Страница 53: ...otorDefault emf 80 08 1 2049 Motor_error emf 08 1 0 2050 Motor_is_off emf 08 1 0 0 2052 motor_is_on emf DIR 10 0 0 0 4096 SimoMotorDefault emf 10 1 4097 Motor_error emf 10 1 0 4098 Motor_is_off emf 10 1 0 0 4100 Motor_is_on emf REV 20 0 0 0 0 8192 SimoMotorDefault emf 20 1 8193 Motor_error emf 20 1 0 8194 Motor_is_off emf 20 1 0 0 8200 Motor_is_rev emf 20 1 0 0 0 8196 Motor_is_forw emf STAR 30 0 0...

Страница 54: ...r emf 50 1 0 20482 Motor_is_off emf 50 1 0 0 20484 motor_is_on emf 50 1 0 0 0 20488 motor_is_slow emf VALVE 60 0 0 0 24576 vho_undef emf 60 1 24577 VHO_error emf 60 1 0 24578 vho_closed emf 60 1 0 0 24580 vho_opened emf POS 70 0 0 0 0 0 0 28672 vho_undef emf 70 1 28673 VHO_error emf 70 1 0 28674 vho_undef emf 70 1 0 0 28676 vho_opened emf 70 1 0 0 0 28680 vho_closed emf 70 0 1 0 28736 vho_closed e...

Страница 55: ...al 09 2019 A5E48307694002A RS AA 001 55 Status display icons Icons Filename MOTOR_Error emf motor_is_forw emf motor_is_off emf motor_is_on emf motor_is_rev emf motor_is_slow emf SimoMotorDefault emf SimoOvl1 emf SimoOvl2 emf SimoOvl3 emf SimoStar1 emf SimoStar2 emf vho_closed emf VHO_Error emf vho_opened emf vho_undef emf ...

Страница 56: ...SIMO_CHN Function 3 6 Display in WinCC SIMOCODE DP PCS 7 Library Migration Legacy V9 0 SP2 56 Programming and Operating Manual 09 2019 A5E48307694002A RS AA 001 ...