Overview of Fail-safe Systems
1.4 Components of S7 Distributed Safety and S7 F/FH Systems
Safety Engineering in SIMATIC S7
System Manual, 04/2006, A5E00109529-05
1-13
Restrictions on the Use of S7-300 Standard SMs
The restrictions for fault-tolerant systems are applicable to the use of S7-300 standard SMs
in S7 F/FH Systems (see
Automation System S7-400H Fault-Tolerant Systems manual).
For the restrictions for S7-300 standard SMs in safety mode of F-SMs, refer to the
Automation System S7-300 Fail-safe Signal Modules manual.
ET 200S Fail-safe Electronic Modules
The following fail-safe electronic modules (F-modules) are available in ET 200S:
•
PM-E F pm 24 VDC PROFIsafe power module with 2 additional fail-safe digital outputs
•
PM-E F pp 24 VDC PROFIsafe power module
•
PM-D F 24 VDC PROFIsafe power module
•
4/8 F-DO 24 VDC PROFIsafe digital electronic module
•
4 F-DO 24 VDC/2 A PROFIsafe digital electronic module
F-modules can not be used with standard CPUs in standard applications.
Interface Modules for ET 200S with Fail-safe Modules
One interface module is required for each ET 200S. The F-system determines which
interface module can be used:
Table 1-4
Use of Interface Modules with ET 200S Fail-safe Modules
Interface Module
Order Number (or higher)
Applicable Optional Package
in ET 200S
Version (or
higher)
S7 Distributed Safety
V5.1
IM 151-1 HIGH
FEATURE
6ES7 151-1BA00-0AB0
6ES7 151-1BA01-0AB0
S7 F Systems
V5.2
IM 151-7 F-CPU
6ES7 151-7FA01-0AB0
S7 Distributed Safety
V5.2
IM 151-3 PN HIGH
FEATURE
6ES7 151-3AB00-0AB0
S7 Distributed Safety
V 5.4
Note
Unlike IM 151-1 HIGH FEATURE, for example, the IM 151-7 F-CPU is an intelligent
preprocessing device (intelligent DP slave) and can also be used as a DP master. An IM
151-7 F/CPU can therefore exercise full and, if necessary, independent control over a
technological functional unit and can be used as a stand-alone CPU or F-CPU. The IM 151-7
F-CPU represents an addition to the line of F-CPUs for S7 Distributed Safety.