Overview of Fail-safe Systems
1.4 Components of S7 Distributed Safety and S7 F/FH Systems
Safety Engineering in SIMATIC S7
1-14
System Manual, 04/2006, A5E00109529-05
ET 200pro Fail-safe Modules
The following fail-safe electronic modules (F-modules for short) are available for an
ET 200pro:
•
8/16 F-DI DC24V PROFIsafe Digital Electronic Module
•
4/8 F-DI/4 F-DO DC24V/2A PROFIsafe Digital Electronic Module
ET 200eco Fail-safe I/O Module
The following fail-safe I/O modules (F-modules) are available in ET 200eco:
•
4/8 F-DI 24 VDC PROFIsafe
Fail-safe DP Standard Slaves
Fail-safe DP standard slaves are standard slaves that are operated on PROFIBUS with the
DP protocol and the PROFIsafe bus profile. Their behavior must comply with IEC 61784-
1:2002 Ed1 CP 3/1 and the PROFIsafe bus profile.
Fail-safe DP standard slaves that are used in a mixed configurations on PROFIBUS DP and
PROFINET IO after IE/PB links, must support the PROFIsafe bus profile in the V2 mode.
A GSD file is used to configure fail-safe DP standard slaves.
Fail-safe IO Standard Devices
Fail-safe I/O standard slaves are standard devices that are operated on PROFINET with the
I/O protocol and the PROFIsafe (V2 mode) bus profile. They must behave in accordance
with IEC 61784-1:2002 Ed1 CP 3/3 and the PROFIsafe bus profile (V2 MODE). A GSDML
file is used to configure them.