Configurations and Help with Selection
2.3 Configuration Variants for Fail-safe Systems According to Availability Requirements
Safety Engineering in SIMATIC S7
2-14
System Manual, 04/2006, A5E00109529-05
Configuration Example of S7 Distributed Safety and PROFINET IO
PROFINET IO
)DLOVDIHPRGXOHV
)DLOVDIHPRGXOHV
(76VLQJOHFKDQQHO
GLVWULEXWHG,2
6VWDWLRQZLWK
&38)31'3
(7SURVLQJOHFKDQQHO
GLVWULEXWHG,2
)DLOVDIH,2VWDQGDUGGHYLFH
Figure 2-10 S7 Distributed Safety with Single-channel I/O (PROFINET IO)
Limits of Availability with Single-channel I/O
In the event of a fault, the I/O are no longer available. The F-I/O is passivated.
Possible fault causes:
•
Failure of F-I/O
•
Failure of interface module in an ET 200M, ET 200S or ET 200pro
•
Failure of the entire ET 200M, ET 200S, ET 200pro or ET 200eco
•
Failure of the PROFIBUS DP or PROFINET IO line
•
Failure of the F-CPU