Overview of All Actions
S7-GRAPH for S7-300/400 Programming Sequential Control Systems
C79000-G7076-C526-01
13-5
Action
Explanation
Address
range
Event
Instruction
Address
Area
Location
S0
CALL
FB, FC,
SFB, SFC
Block
number
As soon as the step is
deactivated (leaves state), the
specified block is called.
S0
ON
S
i
As soon as the step is
deactivated (leaves state),
step i is activated.
i = step
number
S0
OFF
S
i
As soon as the step is
deactivated (leaves state),
step i is also deactivated.
i = step
number
V1: Actions linked to supervision errors entering the state
V1
N
Q,I,M,D*
m.n
As soon as a supervision
error occurs while the step is
active or a supervision error
had been detected before the
step became active, the
signal state of the address is
1.
0.0 to
65535.7
V1
S
Q,I,M,D*
m.n
As soon as a supervision
error occurs while the step is
active or a supervision error
had been detected before the
step became active, the
address is set to 1 and then
remains set to 1.
0.0 to
65535.7
V1
R
Q,I,M,D*
m.n
As soon as a supervision
error occurs while the step is
active or a supervision error
had been detected before the
step became active, the
address is set to 0 and then
remains set to 0.
0.0 to
65535.7
V1
CALL
FB, FC,
SFB, SFC
Block
number
As soon as a supervision
error occurs while the step is
active or a supervision error
had been detected before the
step became active, the
specified block is called.
V1
ON
S
i
As soon as a supervision
error occurs while the step is
active or a supervision error
had been detected before the
step became active, step i is
activated.
0.0 to
65535.7