Functions
4.1 BACnet objects
PN/BACnet LINK
Operating Instructions, 10/2017, A5E39895543-AA
19
Communication paths of BACnet server
BACnet objects of the type "Binary input (BI) and "Analog input" (AI) are inputs on the
BACnet side. The values are written from the S7 side to the "Present_Value" property of the
corresponding input object.
BACnet objects of the type "Binary output (BO) and "Analog output" (AO) are outputs on the
BACnet side. The "Present_Value" properties of the output objects are read from the
S7 side.
With server objects, the PN/BACnet LINK writes the status information transferred by the
S7 controller to the property "Status_Flags" of the corresponding objects.
Figure 4-1
Communication paths of BACnet server