System overview
3.2 Features
PN/BACnet LINK
Operating Instructions, 10/2017, A5E39895543-AA
13
3.2
Features
General features
●
1 BACnet port (Fast Ethernet, RJ45). The maximum transmission rate is 100 Mbps.
●
The PN/BACnet LINK supports BACnet/IP according to DIN EN ISO16484-5 and
Addendum ANSI/ASHRAE Standard 135-2012.
●
BACnet/IP profile: B-GW (BACnet gateway)
●
2 PROFINET interfaces (integrated switch) enable PROFINET line operation according to
Conformance Class B (CC-B).
●
A PN/BACnet LINK can be both a BACnet client and a BACnet server. The actual
functionality of the PN/BACnet LINK is defined when it is configured. A mixed mode of
Client and Server functionality is possible.
●
The PN/BACnet LINK is configured via the corresponding HSP in the TIA Portal.
●
The following options are available for creating BACnet object references:
–
Manual input of the required object addresses
–
Scanning the network with takeover of the selected objects
–
Import a network description (EDE file) and select the desired objects
●
The BACnet server located in the PN/BACnet LINK can handle up to 1000 subscribers.
●
The BACnet client located in the PB/BACnet LINK can establish communication
relationships with up to 126 BACnet devices.
BACnet characteristics
Supported BACnet object types:
●
DEVICE
●
BINARY INPUT
●
BINARY OUTPUT
●
ANALOG INPUT
●
ANALOG OUTPUT
Supported BACnet services:
●
Change of Value COV-A/B
●
ReadProperty RP-A/B
●
WriteProperty WP-A/B
Monitoring of BACnet devices:
●
Cyclic query of the status properties in the device object
●
Set the status in the device object of the PN/BACnet LINK