Functions
4.1 BACnet objects
PN/BACnet LINK
22
Operating Instructions, 10/2017, A5E39895543-AA
4.1.2.1
Device object
Device object properties
Every BACnet device object and also therefore the PN/BACnet LINK has a device object as
logical representation of the device. This object specifies the basic properties of a BACnet
device. Devices in the BACnet network can read out the properties of a BACnet device. For
example, as a BACnet client, the PN/BACnet LINK is able to read the device object from
other devices in the BACnet network.
The following table shows which properties are supported for the device object of the
PN/BACnet LINK and from which source the associated values originate.
Property
Data source
Value
Access
Object_Identifier
Configuration
--
R
Object_Name
Configuration
--
R
Object_Type
Fixed
8
R
System_Status
Dynamic
--
R
Vendor_Name
Fixed
Siemens AG
R
Vendor_Identifier
Fixed
7
R
Model_Name
Fixed
PN/BACnet LINK
R
Firmware_Revision
Fixed
e.g. V1.0.0-xxxx
xxxx = 4-digit build number
R
Application_Software_Version
Configuration
--
R
Protocol_Version
Fixed
1
R
Protocol_Revision
Fixed
13
R
Protocol_Services_Supported
Dynamic
--
R
Protocol_Object_Types_Supported
Dynamic
--
R
Object_List
Dynamic
--
R
Max_APDU_Length_Accepted
Fixed
1476
R
Segmentation_Supported
Fixed
0 = SEGMENTED_BOTH
R
APDU_Timeout
Fixed
6000 (= 6 s)
R
Number_Of_APDU_Retries
Fixed
3
R
Device_Address_Binding
Dynamic
--
R
Database_Revision
Configuration
--
R
Description
Configuration
--
R
Active_COV_Subscriptions
Dynamic
--
R
Apdu segment timeout
Fixed
5000 (= 5 s)
R
Max_Segments_Accepted
Fixed
32
R
R: Read